| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/02/2026 | Commercial Building | APPROVED | |||
| 08/31/2026 | Commercial Electrical | APPROVED | |||
| 09/04/2026 | Site Zoning | APPROVED | |||
| 09/08/2026 | Water - PDSD | APPROVED | |||
| 09/08/2026 | Commercial Mechanical | NOT REQUIRED | |||
| 08/25/2026 | Site Engineering | NOT REQUIRED | |||
| 09/08/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/08/2026 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. The pressure-absorbing devices shall conform to ASSE 1010; an air chamber is not acceptable. Reference: Section 604.9, IPC 2024. 2. Appliances (e.g. beverage dispensers, ice makers, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.14.1, IPC 2024 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2024. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 09/08/2026 | Fire New Construction | REVIEW COMPLETED | |||
| 08/24/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |