Permit Number: TC-COM-0826-01310
Parcel: 13323164A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0826-01310
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2026 Water - PDSD APPROVED
08/25/2026 Site Engineering NOT REQUIRED
09/03/2026 Site Zoning NOT REQUIRED
09/04/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/02/2026 Commercial Building REQUIRES RESUBMIT Renovation of existing Restaurant space inside of Walmart. Adding partition wall, electric outlets, floor sinks, water lines, wall finishes, new equipment
Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Provide a cover sheet or code data sheet. IBC 107.2.1
2. Provide the year/edition and title of all adopted applicable codes, consistent with the jurisdiction’s adopting ordinance. IBC 107.2.1
3. Provide a drawing index identifying all sheets included in this permit’s scope. IBC 107.2.1
4. Provide a detailed description of the work included in this permit’s scope. IBC 105.3
5. Provide an interior finish schedule identifying all new interior finishes. IBC Chapter 8
6. Identify all proposed new walls on the floor plans and provide applicable construction drawings and details for each wall assembly, including required fire-resistance ratings where applicable. IBC 107.2.1

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
08/28/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0826-01310 (7150 E SPEEDWAY BL TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov


1. No shelving above the existing panels, NEC 110.26, 110.26(B), 110.26(E).
Reference Sheet E1.0, Keyed Note #2.
2. Update Electrical Power Note 'I', to include GFCI protection for all OUTLETS for appliances listed at NEC 210.8(D), including the ovens, stoves, and ranges, microwave ovens etc.
3. Provide GFCI protection for all receptacles located at the fountain drink area, NEC 210.8(B)(4).
4. Reference sheet E3.0, MACEC 2019 code references. Remove all references to Massachusetts codes and 2021 energy codes.
Provide compliance with the City of Tucson adopted codes, 2024 ICC codes, 2023 NEC, etc.
5. Provide complete compliance with the 2018 IECC for the interior lighting, including sensors and lighting controls as required. (typically COMcheck.).
09/03/2026 Commercial Mechanical REQUIRES RESUBMIT Provide general room exhaust for any cooking appliance that does not require the installation of a Type II hood (e.g., microwave oven, rapid cook oven, oven/proofer combination, etc.). The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.1, exception 6, IMC 2024.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
09/03/2026 Commercial Plumbing REQUIRES RESUBMIT 1. Appliances (e.g. beverage dispensers, ice makers, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.14.1, IPC 2024 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2024
2. The Plumbing Specification (P3.0) for water disinfection is incomplete. A water disinfection report is required and shall include the results of a bacteriological examination by a licensed testing laboratory of the water in the revised water distribution system after the chlorine has been purged from the system. Section 610.1 of the 2024 International Plumbing Code describes the testing requirements.
3. Provide cleanouts for all horizontal drains; the cleanouts shall be sized per Section 708.1.5, IPC 2024 and shall open to allow cleaning in the direction of flow. Reference: Sections 708.1.1 and 708.1.9, IPC 2024.
4. Provide indirect waste piping for the food prep sink, E51.2. Reference: Section 802.1, IPC 2024.
5. A hand wash sink located in the kitchen area shall either discharge through a grease interceptor or have a sign posted above it stating: “HANDWASH SINK ONLY! NO FOOD PREPARATIONOR DISHWASHING ALLOWED”. Reference: Section 1003.3(A), IPC 2024 as amended by the City of Tucson.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov
09/04/2026 Fire New Construction REQUIRES RESUBMIT -Resolve all building comments.