Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0826-01295
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/19/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/19/2026 | Water Sterilization Report (Deferred Submittal) Express | REQUIRES RESUBMIT | The required water disinfection report shows the presence of coliform bacteria in the water distribution system. Repeat the disinfection procedure until a bacteriological examination by a licensed testing laboratory shows no presence of E. coli or other coliform bacteria. Reference: Section 610.1, IPC 2024. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov |
||
| 10/16/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |