Permit Number: TC-COM-0826-01283
Parcel: 115070750

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0826-01283
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2026 Commercial Building Standard APPROVED
08/21/2026 Commercial Mechanical Standard APPROVED
08/21/2026 Commercial Plumbing Standard APPROVED
08/24/2026 Outdoor Lighting Standard APPROVED outdoor lighting approved under TC-COM-0626-00908 (1742 N ORACLE RD Unit:BLDG 1 TUCSON, AZ 85705)
08/21/2026 Site Engineering Standard APPROVED
08/21/2026 Site Zoning Standard APPROVED
08/24/2026 Water - PDSD Standard APPROVED
08/24/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/21/2026 Commercial Electrical Standard REQUIRES RESUBMIT 1. Sheet E101 Provide the one-line identical to one-line used for the approved plans.
2.Sheet E202 The panel schedule provides compliance with NEC 700.12(H)(2)(3) & (4) but it does not correlate with the floor plan on sheet E302. Please revise the floor plan to correlate with the panel schedule.
3. Sheet E302 The interior exit/egress circuit does not comply with NEC 700.12(H)(2)(3)
08/21/2026 Fire New Construction Standard REVIEW COMPLETED
08/14/2026 PDSD Application Completeness Express REVIEW COMPLETED Main permit TC-COM-0626-00908 is in review and Bluebeam for main permit is 289-856-783 .

There is no valuation added to this permit. Please send the valuation for this project in writing to building_official@tucsonaz.gov .