Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0826-01283
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/21/2026 | Commercial Building Standard | APPROVED | |||
| 08/21/2026 | Commercial Mechanical Standard | APPROVED | |||
| 08/21/2026 | Commercial Plumbing Standard | APPROVED | |||
| 08/24/2026 | Outdoor Lighting Standard | APPROVED | outdoor lighting approved under TC-COM-0626-00908 (1742 N ORACLE RD Unit:BLDG 1 TUCSON, AZ 85705) | ||
| 08/21/2026 | Site Engineering Standard | APPROVED | |||
| 08/21/2026 | Site Zoning Standard | APPROVED | |||
| 08/24/2026 | Water - PDSD Standard | APPROVED | |||
| 08/24/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/21/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | 1. Sheet E101 Provide the one-line identical to one-line used for the approved plans. 2.Sheet E202 The panel schedule provides compliance with NEC 700.12(H)(2)(3) & (4) but it does not correlate with the floor plan on sheet E302. Please revise the floor plan to correlate with the panel schedule. 3. Sheet E302 The interior exit/egress circuit does not comply with NEC 700.12(H)(2)(3) |
||
| 08/21/2026 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 08/14/2026 | PDSD Application Completeness Express | REVIEW COMPLETED | Main permit TC-COM-0626-00908 is in review and Bluebeam for main permit is 289-856-783 . There is no valuation added to this permit. Please send the valuation for this project in writing to building_official@tucsonaz.gov . |