Permit Number: TC-COM-0826-01273
Parcel: 106041770

Address:
520 E MOHAVE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0826-01273
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/12/2026 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0826-01273 (520 E MOHAVE RD TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov


1. Provide an electrical riser diagram, NEC 230.9. Notate the grounding and bonding method, NEC 250.20(B), 250.24, 250.30(A)(4). Metallic gas lines must be bonded and not be used as the primary grounding method, NEC 250.50, 250.52(B)(1).
a. Show each meter and address/unit associated with each meter. (or disconnects)
b. Show bus bar rating and AIC ratings.
2. Provide Service Surge Protection per NEC 230.67. All downstream dwelling units require surge protection when replacing the service equipment.