Permit Number: TC-COM-0826-01267
Parcel: 10824028F

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0826-01267
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2026 Commercial Building Standard APPROVED
09/01/2026 Commercial Mechanical Standard APPROVED
09/01/2026 Commercial Plumbing Standard APPROVED
09/02/2026 Site Zoning Standard APPROVED
09/01/2026 Water - PDSD Standard APPROVED
08/26/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
08/14/2026 Site Engineering Standard NOT REQUIRED
09/02/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/26/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0826-01267 (4001 N COUNTRY CLUB RD TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Show compliance with NEC 210.8(B)(2), (3), (7) for voltage range, current rating by providing GFCI protection for all kitchen and bar receptacles. Readily accessible per 210.8.
2. Provide GFCI protection for all appliance OUTLETS listed in 210.8(D). Readily accessible per 210.8.
3. Show a GFCI [NEC 210.8(E)] receptacle outlet on the same level within 25’ of all new HVAC equipment, [NEC 210.63].
4. Provide conductor sizing and wiring methods for each unit connected to the EXS AC GUTTER. NEC chapter 3.
09/01/2026 Fire New Construction Standard REVIEW COMPLETED
08/12/2026 PDSD Application Completeness Express REVIEW COMPLETED