Permit Number: TC-COM-0826-01264
Parcel: 14118602A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0826-01264
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2026 Commercial Electrical APPROVED
08/26/2026 Commercial Plumbing APPROVED
08/25/2026 Site Zoning APPROVED
08/26/2026 Water - PDSD APPROVED
08/26/2026 Site Engineering NOT REQUIRED
08/26/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/26/2026 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. ANSI Code Edition: Revise the plans to indicate the 2017 ICC A117.1 edition, rather than the 2024 edition. IBC 107.2.1
2. Accessible Seating: Revise the plans to provide accessible dining surfaces for at least 5 percent, but not less than one, of the dining surfaces. Accessible seating shall be distributed throughout the facility and located on a level served by an accessible route. IBC 1109.2.9.1
3. Sales and Service Counters: Revise the plans to provide at least one accessible counter of each type provided for the sale or distribution of goods or services. Indicate whether a parallel or forward approach is provided and show the required accessible counter height and length. IBC 1110.16.2; 2017 ICC A117.1 Sections 904.3.2 and 904.3.3
4. Turning Space: Revise the plans to provide a 67-inch turning space in lieu of the 60-inch turning space shown. 2017 ICC A117.1 Section 304.3.1.1
5. Clear Floor Space: Revise the plans to show accessible clear floor space measuring a minimum of 52 inches in length by 30 inches in width. 2017 ICC A117.1 Section 305.3.1

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
08/26/2026 Commercial Mechanical REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0826-01264
ADDRESS/PARCEL: 10023 E OLD VAIL RD Unit:UNIT 193 TUCSON, AZ 85747

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Please provide heating and cooling load calculations to justify the heating/cooling capacity of the additional 3-ton unit. Reference: Section C403.1.1 and C502.3.3, IECC 2024.
08/24/2026 Fire New Construction REVIEW COMPLETED
08/12/2026 PDSD Application Completeness Express REVIEW COMPLETED