Permit Number: TC-COM-0826-01252
Parcel: 135074550

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0826-01252
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/07/2026 Commercial Electrical Express REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov

1. Please complete the Electrical Reconnect Information sheet
2. Please indicate the size of the service for example 200A
3. Provide a site plan locating the structure and the service location on the structure



Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
08/07/2026 PDSD Application Completeness Express REVIEW COMPLETED