Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0826-01249
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/31/2026 | Commercial Building Standard | APPROVED | |||
| 08/25/2026 | Commercial Electrical Standard | APPROVED | |||
| 09/01/2026 | Site Zoning Standard | APPROVED | |||
| 08/31/2026 | Water - PDSD Standard | APPROVED | |||
| 08/25/2026 | Outdoor Lighting Standard | NOT REQUIRED | No modification to the outdoor lighting. | ||
| 08/12/2026 | Site Engineering Standard | NOT REQUIRED | |||
| 09/01/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/31/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2024. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 08/31/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | 1. To qualify as a point-of-use water dispenser in lieu of a drinking fountain, a bottle filler requires the installation of a listed and labeled dispenser along with a permanently mounted disposable cup dispenser. The cup dispenser shall be located adjacent to the water dispenser with the dispensing end between 34” and 48” above the finished floor. See: https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/2008-21_e_drinkingfountainpolicy.pdf 2. Note: The Elkay bottle filler model LZWSGRN8K has been discontinued by the manufacturer. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov |
||
| 08/31/2026 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 08/11/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |