Permit Number: TC-COM-0826-01246
Parcel: 11004345K

Address:
3315 N SWAN RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0826-01246
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2026 Commercial Building APPROVED
08/14/2026 Commercial Electrical APPROVED
08/24/2026 Water - PDSD APPROVED
08/24/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/24/2026 Commercial Mechanical REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0826-01246
ADDRESS/PARCEL: 3315 N SWAN RD TUCSON, AZ 85712

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Please provide an air balance schedule showing the total supply and exhaust airflow quantities for the building. Demonstrate that the proposed HVAC systems maintain the 150 CFM net positive building pressure. Reference: Section 508.1.3, IMC 2024.
08/24/2026 Commercial Plumbing REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0826-01246
ADDRESS/PARCEL: 3315 N SWAN RD TUCSON, AZ 85712

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. The existing 2-vat fryer is being replaced. Please show all other gas-fired appliances connected to the gas meter as well and the total gas demand seen by the meter. Verify the existing gas piping system is adequately sized for the replacement fryer. Reference: Section 402, IFGC 2024.
08/18/2026 Fire New Construction REVIEW COMPLETED
08/06/2026 PDSD Application Completeness Express REVIEW COMPLETED