Permit Number: TC-COM-0826-01233
Parcel: 13014039B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0826-01233
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2026 Water - PDSD Standard APPROVED
08/27/2026 Commercial Mechanical Standard NOT REQUIRED
08/27/2026 Commercial Plumbing Standard NOT REQUIRED
08/24/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
08/17/2026 Site Engineering Standard NOT REQUIRED
08/31/2026 Site Zoning Standard NOT REQUIRED
08/31/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/28/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Metal Stud to Concrete Connection
Please provide the fastening method and details for connecting the metal stud wall to the existing concrete, including fastener type, size, spacing, and required edge distances. IBC 107.2.1; 2210.1.1.
2. Thin Brick Veneer – Evaluation Report
Please provide the applicable ICC-ES Evaluation Report (ESR) number for the proposed adhered thin brick veneer and identify the approved installation system. IBC 1404.10; 1404.10.1; 107.2.1.
3. Water-Resistive Barrier
Please identify the water-resistive barrier (WRB) behind the adhered thin brick veneer and provide the applicable product information. IBC 1403.2; 1404.10.1.1.
4. Flashing/Screed
Please provide details indicating the required corrosion-resistant flashing/screed at the base of the adhered masonry veneer, including its termination and integration with the WRB. IBC 1404.4; 1404.11.1.2.1
A. On exterior stud walls, adhered masonry veneer shall be installed not less than 4 inches above the earth, or not less than 2 inches above paved areas, or not less than 1/2 inch above exterior walking surfaces that are supported by the same foundation that supports the exterior wall. 1404.11.1.3 Clearances.
5. Adhered Veneer Installation Details
Please provide complete installation details for the adhered thin brick veneer, including the substrate, mortar/adhesive, lath and scratch coat where applicable, and attachment method. IBC 1404.10; manufacturer’s installation instructions.
Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
08/24/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0826-01233 (1401 S ALVERNON WY TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide an electrical plan showing any/all electrical work. Plans shall include but may not be limited to items below and as necessary for the actual scope of work:
2. Electrical demo plans.
3. Provide an electrical panel schedule and designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1.
4. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.
08/25/2026 Fire New Construction Standard REQUIRES RESUBMIT -Please update your code analysis. You currently show two exits provided. Are you providing two exits or three? Please explain your exiting intentions of the south door.
-Provide more detail on your locking mechanism on the south door. Are you controlling egress? Will this be a delayed egress locking system or controlled egress? Provide which type of exiting you will comply with. Either comply with 1010.2.10, 10102.11 or 1010.2.12 of the IFC. Clearly state on the drawings, which code you will comply with.
-Exits shall be not less than one half of the length of the maximum overall diagonal dimension of the building or area served (non-sprinklered). IFC 1007.1.1
-Please provide a response to all comments.
john.vincent@tucsonaz.gov
5203495581