Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0826-01231
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/29/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/29/2026 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0826-01231 ADDRESS/PARCEL: 9130 E VALENCIA RD TUCSON, AZ 85747 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov COMMENTS: 1. The submitted air balance report does not reflect the correct design exhaust CFM. The design exhaust CFM was changed from 980 CFM to 910 CFM on the most recent submittal. Please submit a revised air balance report reflecting the correct design exhaust CFM and confirming it is within the engineer’s specified tolerances. |
||
| 10/29/2026 | County Health Inspection (Deferred Submittal) Express | REVIEW COMPLETED | |||
| 10/29/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |