Permit Number: TC-COM-0826-01230
Parcel: 124050520

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0826-01230
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/29/2026 Design Review Standard REQUIRES RESUBMIT If the Main Gate District Urban Overlay Zone (MGD) will be pursued for the change of land use from Food Service to Alcoholic Beverage Service, please submit a complete Design Package following these instructions: https://www.tucsonaz.gov/files/sharedassets/public/v/3/pdsd/documents/submission-documents/special_districts_application_instructions_7.18.23.pdf. If you have any questions, please let me know: maria.gayosso@tucsonaz.gov. Thank you.
09/21/2026 Fire New Construction Standard REQUIRES RESUBMIT -Please revise the two inward swinging exit doors. If these doors are designated exits, with signage above doors, they also need to comply with all the exiting requirements. Otherwise, remove the exit door signs that are shown above the doors.
john.vincent@tucsonaz.gov
5203495581
09/24/2026 Site Zoning Standard REQUIRES RESUBMIT FROM: Olga Salazar
PDSD Zoning Review Section

PROJECT: TC-COM-0826-01230 – Bar
Tenant Improvement (2nd Review)
820 E UNIVERSITY BLVD – C-1 Zoning

TRANSMITTAL DATE: September 24, 2026

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: The underlying zoning is C-1 which does not permit Commercial – Alcoholic Beverage Services (bar). The site is in the Urban Overlay District – Main Gate District which allows Alcoholic Beverage Services (Main Gate District Section C-2, sheet 9). To allow the proposed use, an approved application from Special Districts is required. Zoning approval is contingent upon this approval.

2. COMMENT: More comments may be forthcoming based on the next submittal's response.


If you have any questions about this transmittal, please contact Olga.Salazar@tucsonaz.gov.
09/11/2026 PDSD Application Completeness Express REVIEW COMPLETED