Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0826-01222
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2026 | Commercial Electrical Express | APPROVED | |||
| 08/03/2026 | Addressing Validation | REQUIRES RESUBMIT | If you have questions regarding this Review, please email at PDSD-Permits@tucsonaz.gov Please resubmit addressing the following comments: The address on the permit application and the plans do not match. Please revise address on plans. If the address on the permit application needs to be changed, submit a Change of Address Request to update address. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/sub-records_071425.pdf |
||
| 08/03/2026 | Commercial Mechanical Express | REQUIRES RESUBMIT | 1. Verify that the proposed heat rejection chiller complies with the minimum efficiency requirement for liquid-cooled, electrically operated centrifugal chillers. Reference: Table C403.3.2(3), IMC 2024. 2. Show how the emergency exhaust flow rate of 3800 CFM for EF-3 was determined. Reference: Section 1105.6.3.2, IMC 2024. 3. .Show the location of the chiller pressure relief discharge with respect to building openings. Reference: Section 1105.7, IMC 2024. 4. Provide specification section 23 6000 for safety relief devices (noted in detail 1/M09.01). Reference: Section 1105.8, IMC 2024. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 08/03/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |