Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-0826-01222
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/05/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/05/2026 | Commercial Mechanical Express | REQUIRES RESUBMIT | The existing wall louver is an opening to the building. Both the relief vent discharge and the emergency exhaust duct discharge shall be located “not less than 20 feet (6096 mm) from any window, ventilation opening or exit.” Reference: Section 1105.7, IMC 2024. [Initial comment: Show the location of the chiller pressure relief discharge with respect to building openings. Reference: Section 1105.7, IMC 2024.] If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||