Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0826-01222
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/05/2026 Commercial Mechanical Express REQUIRES RESUBMIT The existing wall louver is an opening to the building. Both the relief vent discharge and the emergency exhaust duct discharge shall be located “not less than 20 feet (6096 mm) from any window, ventilation opening or exit.” Reference: Section 1105.7, IMC 2024. [Initial comment: Show the location of the chiller pressure relief discharge with respect to building openings. Reference: Section 1105.7, IMC 2024.]