| 09/23/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. Calculation of the required minimum ventilation for air handlers serving multiple zones requires the balancing data (supply CFM) for each zone and the calculations described in Sections 403.3.1.1.2.3.1 through 403.3.1.1.2.3.4, IMC 2018. (Note: a library does not have the same ventilation requirements as a preschool classroom.) Reference: Section 403.3.1.1.2.3, IMC 2018. 2. The submitted ventilation calculations include a gym: where is it located? Reference: Section 107.2.1, IMC 2018. |
||