Permit Number: TC-COM-0825-01603
Parcel: 12218266A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0825-01603
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2025 Commercial Building Standard APPROVED
09/12/2025 Commercial Electrical Standard APPROVED
09/23/2025 Commercial Plumbing Standard APPROVED
09/26/2025 Site Zoning Standard APPROVED
09/23/2025 Water - PDSD Standard APPROVED
09/12/2025 Outdoor Lighting Standard NOT REQUIRED No changes to the outdoor lighting.
09/16/2025 Site Engineering Standard NOT REQUIRED
09/26/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/23/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Calculation of the required minimum ventilation for air handlers serving multiple zones requires the balancing data (supply CFM) for each zone and the calculations described in Sections 403.3.1.1.2.3.1 through 403.3.1.1.2.3.4, IMC 2018. (Note: a library does not have the same ventilation requirements as a preschool classroom.) Reference: Section 403.3.1.1.2.3, IMC 2018.
2. The submitted ventilation calculations include a gym: where is it located? Reference: Section 107.2.1, IMC 2018.
09/18/2025 Fire New Construction Standard REVIEW COMPLETED
09/05/2025 PDSD Application Completeness Express REVIEW COMPLETED