Permit Number: TC-COM-0825-01600
Parcel: 10707007D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0825-01600
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/30/2025 Commercial Building Standard REQUIRES RESUBMIT September 30, 2025
2nd Review

Intertech Architectural Interiors
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85712

Re: WEIR MINERALS
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0825-01600
Stantec Project Number: 185215066
Stantec File Number: TUC-25-092

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
F-1 V-B 16,703 63 Yes Yes
B 29
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors, high-strength bolts, field welding.

ARCHITECTURAL COMMENTS

General

1. Addressed.


2. New Comment: The latest submittal did not include the special inspection certificate that was included in the 1st submittal. Please ensure in the next submittal all documents are reuploaded into the City’s permit portal which should include:
a. Construction documents
b. Structural calculations
c. Special inspection certificate
d. Response letter

STRUCTURAL COMMENTS

General

1. Addressed.

Sheet S3

1. Previous Comment: The structural details do not indicate an offset footing design. The architectural sheets indicate multiple offset footings. Please coordinate with the architectural floor plan and provide the additional footing design/s. Still Required: The structural calculations provided do include the offset footings, but a corresponding detail was not provided in the construction documents. Please revise.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
09/30/2025 Commercial Electrical Standard REQUIRES RESUBMIT September 30, 2025
2nd Review

Intertech Architectural Interiors
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85712

Re: WEIR MINERALS
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0825-01600
Stantec Project Number: 185215066
Stantec File Number: TUC-25-092

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
F-1 V-B 16,703 63 Yes Yes
B 29
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors, high-strength bolts, field welding.

ARCHITECTURAL COMMENTS

General

1. Addressed.


2. New Comment: The latest submittal did not include the special inspection certificate that was included in the 1st submittal. Please ensure in the next submittal all documents are reuploaded into the City’s permit portal which should include:
a. Construction documents
b. Structural calculations
c. Special inspection certificate
d. Response letter

STRUCTURAL COMMENTS

General

1. Addressed.

Sheet S3

1. Previous Comment: The structural details do not indicate an offset footing design. The architectural sheets indicate multiple offset footings. Please coordinate with the architectural floor plan and provide the additional footing design/s. Still Required: The structural calculations provided do include the offset footings, but a corresponding detail was not provided in the construction documents. Please revise.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
09/30/2025 Commercial Mechanical Standard REQUIRES RESUBMIT September 30, 2025
2nd Review

Intertech Architectural Interiors
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85712

Re: WEIR MINERALS
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0825-01600
Stantec Project Number: 185215066
Stantec File Number: TUC-25-092

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
F-1 V-B 16,703 63 Yes Yes
B 29
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors, high-strength bolts, field welding.

ARCHITECTURAL COMMENTS

General

1. Addressed.


2. New Comment: The latest submittal did not include the special inspection certificate that was included in the 1st submittal. Please ensure in the next submittal all documents are reuploaded into the City’s permit portal which should include:
a. Construction documents
b. Structural calculations
c. Special inspection certificate
d. Response letter

STRUCTURAL COMMENTS

General

1. Addressed.

Sheet S3

1. Previous Comment: The structural details do not indicate an offset footing design. The architectural sheets indicate multiple offset footings. Please coordinate with the architectural floor plan and provide the additional footing design/s. Still Required: The structural calculations provided do include the offset footings, but a corresponding detail was not provided in the construction documents. Please revise.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
09/30/2025 Commercial Plumbing Standard REQUIRES RESUBMIT September 30, 2025
2nd Review

Intertech Architectural Interiors
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85712

Re: WEIR MINERALS
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0825-01600
Stantec Project Number: 185215066
Stantec File Number: TUC-25-092

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
F-1 V-B 16,703 63 Yes Yes
B 29
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors, high-strength bolts, field welding.

ARCHITECTURAL COMMENTS

General

1. Addressed.


2. New Comment: The latest submittal did not include the special inspection certificate that was included in the 1st submittal. Please ensure in the next submittal all documents are reuploaded into the City’s permit portal which should include:
a. Construction documents
b. Structural calculations
c. Special inspection certificate
d. Response letter

STRUCTURAL COMMENTS

General

1. Addressed.

Sheet S3

1. Previous Comment: The structural details do not indicate an offset footing design. The architectural sheets indicate multiple offset footings. Please coordinate with the architectural floor plan and provide the additional footing design/s. Still Required: The structural calculations provided do include the offset footings, but a corresponding detail was not provided in the construction documents. Please revise.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
09/29/2025 PDSD Application Completeness Express REVIEW COMPLETED