Permit Number: TC-COM-0825-01594
Parcel: 115043060

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0825-01594
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2025 Site Zoning Standard APPROVED
09/22/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/18/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please amend the occupant load factors to match the values in IBC Table 1004.5 of 20 SF per person for the E occupancies.
A. Alternatively, the occupant load can be increased as long as a furniture/ seating diagram is provided and is showing aisle width. Please be sure to include the teacher and their desks. The diagram will be used to confirm that all occupants have access to an exit, and the exits provide sufficient capacity for all occupants. IBC 1004.5.1 Further, if the increased occupancy is used and approved, the diagram shall be posted in each classroom.
2. Please clarify what the gross area of Existing Building #1 is including, and why is it included on these plans. IBC 107.2.1
3. Please provide a code data for completing the C of O - Type of construction, all occupancies, fire sprinklers yes or no IBC 107.2.1

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
09/17/2025 Fire New Construction Standard REQUIRES RESUBMIT -Please explain the discrepancy with the square footage. Your drawings show the gross as 1448sqft. Your OL chart shows 839sqft. Is 839 the net? Seems to be a large difference.
-Please review the OL factor for classroom. Table 1004.5 IBC shows a factor of 20 for educational classrooms. Your table shows a factor of 15.
john.vincent@tucsonaz.gov
5203495581
08/27/2025 PDSD Application Completeness Express REVIEW COMPLETED