Permit Number: TC-COM-0825-01576
Parcel: 10408090E

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0825-01576
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2025 Commercial Electrical Standard APPROVED
09/18/2025 Site Zoning Standard APPROVED
09/17/2025 Water - PDSD Standard APPROVED
09/18/2025 Site Engineering Standard NOT REQUIRED
09/18/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/18/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please provide structural design, calculations and construction drawing details for the attachment and connection of the new high-speed doors to the existing structure. IBC 107.2.7
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
09/17/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified new HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
2. The control note for the proposed exhaust fan, EF-1, states that the fan will operate only when the gas detection system triggers an alarm. Section 502.13, IMC 2018 requires the exhaust fan to operate continuously unless an automatic exhaust system provides for a minimum exhaust airflow rate of 0.05 CFM per square foot when the space is not in an alarm status. Reference: Section 404.1, IMC 2018.
3. Verify that vehicle engines will only be operated for the purpose of moving the vehicles into or out of the shop. Reference: Section 502.14, IMC 2018.
09/17/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Revise the natural gas riser diagrams to show the size(s) of the gas piping from the meter to the two 1-1/4” branches shown on detail 1/P401. Reference: Sections 402.1 and 402.3, IFGC 2018.
09/16/2025 Fire New Construction Standard REVIEW COMPLETED
08/25/2025 PDSD Application Completeness Express REVIEW COMPLETED