Permit Number: TC-COM-0825-01567
Parcel: 12213060A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0825-01567
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2025 Commercial Electrical APPROVED
09/10/2025 Commercial Plumbing APPROVED
09/08/2025 Site Zoning APPROVED
09/10/2025 Water - PDSD APPROVED
09/10/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/10/2025 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please amend the plans to update the occupancy to include B for the indoor eating portion of this space. IBC 302.1.1
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
09/09/2025 Commercial Mechanical REQUIRES RESUBMIT 1. Provide a site plan that shows the location of the building on the site with the distances from the building to the lot lines drawn in accordance with an accurate boundary line survey. Reference: Section 107.2.6, IBC 2018 and Sections 501.3.1 and 506..13.3 (exception), IMC 2018.
2. Provide the structural details noted on detail 101/M2 to show the construction of the platform supporting exhaust fan, EF-2, and how the platform is to be connected to the building structure. Reference: Section 302.1, IMC 2018.
09/03/2025 Fire New Construction REQUIRES RESUBMIT -It appears this is a market that serves food and drink for consumption along with the market. If so, this would be a mixed use M/B. It would be an A2 however the OL is < than 50 which allows it to be an B. Please correct the occupancy classification or explain the use. 2024 IFC 203.2.7, 203.2.1
john.vincent@tucsonaz.gov
5203495581
09/03/2025 Site Engineering REQUIRES RESUBMIT 1. This project resides within the Alvernon Wash COT floodplain and will require a floodplain use permit with cost estimate to be submitted.
2. The FPU permit can be submitted within the sub-records of this commercial permit. Ensure that the cost estimate of materials and labor from your contractor in the form of a pdf attachment be submitted to complete the FPU application. Please have separate lines for the cost of materials, cost of labor, and any administrative fees or warranties.
08/22/2025 PDSD Application Completeness Express REVIEW COMPLETED