Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0825-01565
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/17/2025 | Commercial Building Standard | APPROVED | |||
| 09/08/2025 | Commercial Electrical Standard | APPROVED | |||
| 09/18/2025 | Site Zoning Standard | APPROVED | |||
| 09/15/2025 | Water - PDSD Standard | APPROVED | |||
| 09/08/2025 | Outdoor Lighting Standard | NOT REQUIRED | No modifications to the outdoor lighting. | ||
| 09/03/2025 | Site Engineering Standard | NOT REQUIRED | |||
| 09/18/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/15/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. Provide heating and cooling load calculations that justify the capacities of the additional heating and cooling equipment specified for the project. Reference: Sections R302.2 and R403.7, IECC 2018 as amended by the City of Tucson. 2. Provide the amount of compressed oxygen being stored in the medical gas storage room. If the amount stored exceeds 504 cubic feet at NTP, verify that the interior medical gas storage room complies with the construction requirements of Section 502.9.1, IMC 2018. Reference: Table 105.6.8, IFC 2018. |
||
| 09/15/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Identify the method used to maintain the temperature of the hot water distribution system. Reference: Section C404.6, IECC 2018 | ||
| 09/10/2025 | Fire New Construction Standard | REQUIRES RESUBMIT | -Update applicable codes, sheet TS-1. TFD/COT has adopted IFC 2024 ed. -Please explain surgical procedures. Will this be considered a B (ambulatory care) per the definition? -It appears there is an interior med gas room between the mechanical room and restroom-2. Provide type and quantities of gas to be used and stored in this room. Quantitates could result the interior room to comply with IFC 5306.2, 5306.2.1. If so, show on drawings all the requirements of these code references. john.vincent@tucsonaz.gov 5203495581 |
||
| 08/22/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |