Permit Number: TC-COM-0825-01565
Parcel: 10824086A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0825-01565
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2025 Commercial Mechanical Standard APPROVED
11/10/2025 Commercial Plumbing Standard APPROVED
11/10/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/07/2025 Fire New Construction Standard REQUIRES RESUBMIT 1. It appears this is a B-ambulatory care facility occupancy per the definition. I believe you meet the definition of an ambulatory care facility. Please add this to your project code check, sheet TS1 as the type of occupancy. Also add a note that you will be installing a fire alarm per IFC 2024 907.2.2 that is required for ambulatory care facilities. Explain your position if you do not agree. Defin: Ambulatory care facility. Buildings or portions thereof used to provide medical, surgical, psychiatric, nursing or similar care on a less than 24 hour basis to persons who are rendered incapable of self preservation by the services provided or staff has accepted responsibility for care recipients already incapable. Defin: Incapable of self preservation. Persons who, because of age , physical limitations, mental limitations, chemical dependency or medical treatment, cannot respond as an individual to an emergency situation.
2. Your medical gas exceeds the amounts listed in IFC table 105.5.9 which requires an operational permit and requires med gas compliance per IFC 5306.2. This section has requirements for interior gas rooms (5306.2.2) that also has mechanical ventilation requirements. Please review this section and provide/show all requirements on your drawings (1hr vertical and horizontal ratings separating it from the remainder of the building, door assembly requirements, and mechanical requirements).
john.vincent@tucsonaz.gov
5203495581
10/21/2025 PDSD Application Completeness Express REVIEW COMPLETED