Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0825-01562
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/21/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/21/2025 | Commercial Mechanical Express | REQUIRES RESUBMIT | Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018. | ||
| 08/21/2025 | Commercial Plumbing Express | REQUIRES RESUBMIT | Provide pipe sizing calculations for natural gas supply to AHU-08, demonstrating conformance to Sections 402.1 and 402.3, IFGC 2018. | ||
| 08/20/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |