Permit Number: TC-COM-0825-01552
Parcel: 13225066A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0825-01552
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2026 Commercial Building Standard APPROVED
01/06/2026 Commercial Electrical Standard APPROVED
01/14/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/06/2026 Commercial Plumbing Standard REQUIRES RESUBMIT The vent for the grease interceptor shall rise vertically to at least 6” above the flood rims of the grease interceptor prior to running horizontally (i.e., the vent needs to connect to the interceptor drain closer to the nearest wall). Reference: Section 905.4, IPC 2018. [Initial comment: The break room includes fixtures that apparently have been added since the last building permit was approved. Provide sealed drawings to show that all of the existing plumbing fixtures and piping have been installed in compliance with the current plumbing code. Reference: Section 107.2.1, IBC 2018.]
12/30/2025 PDSD Application Completeness Express REVIEW COMPLETED