Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0825-01548
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/19/2025 | PDSD Application Completeness Express | REQUIRES RESUBMIT | Incomplete submittal; equipment is 7 years old and amperage is 1000A. Please submit new electrical plans sealed by an engineer. Please indicate if the "like for like" equipment is campatible with the existing equipment (determination needs to be made by the EOR). Please include specification sheets for the new equipment and the AIC rating of the new equipment. Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf For questions: Building_Official@tucsonaz.gov |