Permit Number: TC-COM-0825-01506
Parcel: 13405119H

Address:
9401 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0825-01506
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2025 Commercial Building Standard APPROVED
08/25/2025 Commercial Electrical Standard APPROVED
09/04/2025 Site Zoning Standard APPROVED
08/21/2025 Outdoor Lighting Standard NOT REQUIRED No modifications to the Outdoor Lighting.
08/29/2025 Site Engineering Standard NOT REQUIRED
09/09/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/04/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Clarify why sink PL1F does not have a direct connection. Reference: Sections 301.3 and 802.1, IPC 2018.
2. Clarify the relationship of the 2” combination waste and vent fixture drain from sink PL1F, the existing 2” fixture drain (?) for the existing floor sink and the 2” branch drain. Reference: Section 901.2.1, IPC 2018.
3. Verify the size and total number of fixture units that will be served by the combination waste and vent referenced in keynote #1, on P1.2. Reference: Section 905.2.2, IPC 2018.
09/04/2025 Commercial Mechanical Standard REVIEW COMPLETED
09/02/2025 Fire New Construction Standard REVIEW COMPLETED
08/13/2025 PDSD Application Completeness Express REVIEW COMPLETED
09/04/2025 Water - PDSD Standard REVIEW COMPLETED