Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0825-01504
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/03/2025 | Site Zoning Standard | APPROVED | |||
| 09/04/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/27/2025 | Commercial Building Standard | REQUIRES RESUBMIT | See Master Permit TC-COM-0825-01496 for Comments. | ||
| 08/27/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | See Master Permit TC-COM-0825-01496 for Comments. | ||
| 08/27/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | See Master Permit TC-COM-0825-01496 for Comments. | ||
| 08/27/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | See Master Permit TC-COM-0825-01496 for Comments. | ||
| 08/27/2025 | Fire New Construction Standard | REQUIRES RESUBMIT | -Resolve all building comments. -COT/TFD has adopted 2024 IFC. Please correct the referenced code on sheet T1.1.1 john.vincent@tucsonaz.gov 5203495581 |
||
| 08/20/2025 | Outdoor Lighting Standard | REQUIRES RESUBMIT | Outdoor Lighting Review (770 N KOLB RD TUCSON, AZ 85710) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). Outdoor Lighting Review: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf 1. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. This Outdoor Lighting Plan shall include all light sources for the entire parcel, all new and existing lighting fixtures. Show/locate the different light sources on your site plan. Number the light fixtures on your lighting fixture table and use the same number on your site plan. 2. List the Lighting Area per OLC chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 3. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations, both new and existing. List shielded and unshielded lights in the calculation. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. 4. Show lamps with a maximum of 3500K color temperature, OLC 402.1. 5. Fixtures installed under canopies and overhangs. Outdoor lighting fixtures shall not be counted in determining the total light output when they are full cutoff light fixtures installed under canopies, building overhangs, or roof eaves, OLC 401.2.1(3). 6. Provide manufacture’s specification sheets for outdoor lighting fixtures. 7. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf 8. Specify any exceptions used. 9. Provide Curfew lighting controls If applicable Per section 403 and Table 601.3. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 08/28/2025 | Site Engineering Standard | REQUIRES RESUBMIT | Master Permit has site engineering comments TC-COM-0825-01496 | ||
| 08/12/2025 | PDSD Application Completeness Express | REVIEW COMPLETED | |||
| 09/04/2025 | Water - PDSD Standard | REVIEW COMPLETED |