Permit Number: TC-COM-0825-01486
Parcel: 111062860

Address:
3441 E GLENN ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0825-01486
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/08/2025 Addressing Validation REQUIRES RESUBMIT Permit shows 5 unit meter upgrade. It appears aerial view submitted is not on the same parcel. Unit(s) will have to be confirmed and assigned to Permit Application and on plan prior to issuance. Please sign into your TDC account and request a change of address to include units and re-submit plan with updated addresses.
08/08/2025 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0825-01486 (3441 E GLENN ST TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provide Fault Current Analysis and show new equipment AIC rating sufficient to withstand the calculated Fault Current. Provide Available Fault Current calculations from TEP transformers to all new equipment, 2017 NEC 110.24.
3. Show new Panels and other new equipment with AIC ratings greater than or equal to the Available Fault Currents calculated, 2017 NEC 110.10.
4. Provide electrical load calculations, for the Main Service and sub-panel, Per NEC 220.40.
5. Show the location of the panel on the Electrical Plan with clear working space compliance, 2017 NEC 110.26(A). The location of the panel shown is on a separate parcel and building from the address provided.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov