Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0825-01482
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/18/2025 | Commercial Electrical Standard | APPROVED | |||
| 08/15/2025 | Outdoor Lighting Standard | APPROVED | |||
| 08/28/2025 | Site Zoning Standard | APPROVED | |||
| 09/02/2025 | Water - PDSD Standard | APPROVED | |||
| 09/02/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/02/2025 | Commercial Building Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0825-01482 ADDRESS/PARCEL: (2937 N FLANWILL BL Unit:BLDG 6 TUCSON, AZ 85716) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. COMMENTS: 1. OCCUPANT LOAD CALCULATION (Please provide the accurate occupant load calculation.) a. On your Floor Plan, please add the following. b. You correctly categorized the main spaces as A-3. c. On each space add the following below the name of the space: i. For example, “Residents Lounge”, add below it: 1. 600 sf 2. 15 sf per person 3. 40 occupants d. Please do the same with “Laundry” as A-3. e. B for the Office f. S for the storage g. NOTE: add the occupant load then round up only on this final total row 2. Item 7 Sheet TS1 a. Update to reflect the accurate occupant load calculation from item #1 above. 3. Item 9 Sheet TS1 a. Plumbing Fixtures i. Correct to reflect item #1 above. 4. Detail 10 Sill Plate at Grade Sheet A4 a. Correct 4 inches from weep screed to finish grade (your drawing show it to the top of concrete footing. 5. Weep Screed at covered patio. a. Please provide a detail drawing where patio meets the stucco wall. b. Is a concrete curve proposed at this location to comply with the building code, weep screed 2 inches to the hardscape below. 6. Please resubmit. Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976 |
||
| 09/02/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | The ventilation calculation shows that the resident lounge is calculated as a “bedroom/living room” with a population of 5.6 people. Calculate the space as an “office reception area” (or possibly “correctional, day room”) from Table 03.3.1.1, IMC 2018. Reference: Section 403.3.1.1, IMC 2018. | ||
| 09/02/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Coordinate the sewer and vent riser on P4 with the plumbing plan, i.e. show two lavatories (P-2). | ||
| 08/25/2025 | Site Engineering Standard | REQUIRES RESUBMIT | Permit: TC-COM-0825-01482 Location: 2937 N FLANWILL BL BLDG 6 Review Date: 8/25/2025 Site Engineering Comments: 1. Revise the plans to denote the Finished floor elevation FFE that was included from the development package TD-DEV-0823-00376. 2. This commercial permit will require that a floodplain use permit with elevation certificate be submitted and approved before final site engineering approval is given for permit TC-COM-0825-01482. Ensure that the plans are submitted with the provided FFE’s for the submission of the floodplain use permit. 3. The floodplain use permit can be submitted for within the sub records of each individual commercial permit If you have any questions or concerns, please contact Marco Contreras Marco.contreras@tucsonaz.gov |
||
| 08/27/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 08/07/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |