Permit Number: TC-COM-0825-01449
Parcel: 11104210N

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0825-01449
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2025 Site Engineering Standard NOT REQUIRED
08/25/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/20/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please provide a detailed description of the scope of work included in this permit and provide a complete code analysis. IBC 107.2.1
2. Please submit a current set of construction drawings in accordance with our Commercial Submittal Requirements. IBC 107.2.1 https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
3. It doesn't appear the work shown on the drawings dated June 05, 2008 was ever submitted for a permit. Please provide any documentation that this work was permitted in the past.

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
08/14/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0825-01449 (3501 E FORT LOWELL RD TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).


1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provide updated and current plan-set showing what is currently built.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
08/22/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. I have been unable to find evidence in our records of the current documents having been submitted for a permit in 2008 (e.g. was it ever assigned an activity number?). If the design was not submitted for review in 2008, it will have to be reviewed for compliance with the current building codes.
2. Provide the specifications and installation details for the gas-fired infrared heaters, including the design of the natural gas piping. Reference: Section 107.2.1, IBC 2018.
3. Provide the specifications and operation details for the exhaust fans, EF-1. Reference: Section 107.2.1, IBC 2018.
08/14/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0825-01449 (3501 E FORT LOWELL RD TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).


1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provide updated and current plan-set showing what is currently built.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
08/25/2025 Site Zoning Standard REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0825-01449
3501 E FORT LOWELL RD. - C-3
Food Service (1st Review)

TRANSMITTAL DATE: ‎August 25, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

The site is in the C-3 zone (UDC 4.7.22). Food Service is an allowed use in the zone (UDC Table 4-8-4).

1. Based on plans available online there has been a reconfiguration of the vehicle use area. Either provide a copy of an approved site plan that matches the configuration of the site plan provided in this plan set or a Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/18/2025 Fire New Construction Standard REVIEW COMPLETED
08/01/2025 PDSD Application Completeness Express REVIEW COMPLETED