Permit Number: TC-COM-0825-01448
Parcel: 12405016A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0825-01448
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/20/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved.
1. Please amend the plans to show an exterior landing with a minimum length of 44 inches. The landing shall have a width not less than the width of the stairway or the door, whichever is greater and the same elevation as the interior floor. IBC 1010.1.5 & 1010.1.6
2. Please indicate the width of the T1-11 and verify the nail size and spacing in the field as they do not appear to agree with table IBC Table 2304.6.1 and calculations were not provided.
3. Please provide landing for permit TC-COM-0525-01048 as it was approved in error and this will be addressed either on the next review or in the field. This was not discovered in the first review as a plan view drawing was not provided.
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
08/12/2025 Historic REQUIRES RESUBMIT Based on staff review for completeness here are my comments: (1) Please provide required documents listed in the Historic & Special Districts informational handout (https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/submission-documents/special_districts_application_instructions_7.18.23.pdf) under the Full Review.
(2) Please provide a project narrative based on UDC Section 5.8.9
(https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/planning-amp-zoning/checklist_for_historic_design_review_-_general.pdf). Provide 2-3 sentences on each item. If the item does not apply, note as such.
(3) Revise the plan to include a Development Zone Map showing contributing and non-contributing properties using Historic Map Tucson
https://maps2.tucsonaz.gov/html5viewer/?viewer=historicproperties
A boundary should be drawn around the Development Zone to clearly mark it.
(4) Once revised, please resubmit the historic Design Package under Historic sub record [SD-0825-00120], as a single compressed pdf file.
See link below for steps on resubmitting.
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
If you have any questions, contact Michael.Taku@tucsonaz.gov
08/25/2025 Site Zoning Standard REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0825-01448
1524 S COLUMBUS BL. – HR-3
New exterior door and siding– Multifamily (1st Review)

TRANSMITTAL DATE: August 25, 2025

Resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

This site is located in the HR-3 zone (UDC 4.7.12). A multifamily is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6.

COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8).

1. Exterior work requires Historic review. Historic review (UDC 5.8.8) is required and must be approved prior to approval of this building plan. Historic application/requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Historic-Preservation.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/01/2025 PDSD Application Completeness Express REVIEW COMPLETED