Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0825-01447
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/12/2025 | Site Zoning | APPROVED | |||
| 08/18/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/12/2025 | Commercial Building | REQUIRES RESUBMIT | August 12, 2025 1st Review Trident Building Solutions, Inc. Attn: Susan Rancifer 8215 Roswell Road, Bldg. 100 Atlanta, Georgia 30350 Re: RADIOLOGY LTD – CAMP LOWELL TENANT IMROVEMENT City of Tucson Permit Number: TC-COM-0825-01447 Stantec Project Number: 185215066 Stantec File Number: TUC-25-083 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms N/A N/A 956 N/A N/A N/A Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: Concrete. ARCHITECTURAL COMMENTS Sheet A0.00 1. Please provide a complete code analysis for the project. The code analysis should include the Occupancy Group for the existing building, construction type, occupant load, if existing fire sprinklers/alarms are installed, etc. [Ref. IBC 2018 Sec. 107.2.1] 2. Note on the cover of the drawings that special inspection is required for concrete. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. 3. Please revise the applicable codes for this project to the 2018 International Codes as adopted by the City of Tucson. The 2024 codes indicated are not what the City of Tucson has currently adopted. 4. Please clarify if the building is equipped with an existing fire sprinkler and fire alarm system. If it is, please be sure to indicate on the cover sheet that the modification of the existing systems will be submitted as a separate permit (not deferred submittal). STRUCTURAL COMMENTS General 1. Please provide the structural calculations for the structural design. Sheet S1.00 1. Please submit the shop drawings for the proposed wood I-joists that indicate both joist end connections. If this is intended to be a deferred submittal, please be sure to list the wood I-joists as a deferred submittal on the cover page of the plans and include the following notes: PER IBC Section 107.3.4 <Name of Registrant>, the registered design professional in charge shall be responsible for reviewing and coordinating submittal documents prepared by others, including phased and deferred submittal items, for compatibility with the design of the building. PER IBC Section 107.3.4.1 Submittal documents for deferred submittal items shall be submitted to the registered design professional in responsible charge, who shall review them and forward them to the Building Official with a notation indicating that the deferred submittal documents have been reviewed and that they have been found to be in general conformance with the design of the building. MECHANICAL COMMENTS 1. Please provide updated outside air mechanical calculations. [Ref. IMC 2018 Sec. 403.2] PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS Sheet E1.01 1. Please provide the MRI equipment supplier drawings as referenced in the electrical plan. 2. Please provide an updated interior lighting energy conservation compliance report for the remodeled space. [Ref. IECC 2018 Sec. 405.3] Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 08/12/2025 | Commercial Electrical | REQUIRES RESUBMIT | August 12, 2025 1st Review Trident Building Solutions, Inc. Attn: Susan Rancifer 8215 Roswell Road, Bldg. 100 Atlanta, Georgia 30350 Re: RADIOLOGY LTD – CAMP LOWELL TENANT IMROVEMENT City of Tucson Permit Number: TC-COM-0825-01447 Stantec Project Number: 185215066 Stantec File Number: TUC-25-083 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms N/A N/A 956 N/A N/A N/A Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: Concrete. ARCHITECTURAL COMMENTS Sheet A0.00 1. Please provide a complete code analysis for the project. The code analysis should include the Occupancy Group for the existing building, construction type, occupant load, if existing fire sprinklers/alarms are installed, etc. [Ref. IBC 2018 Sec. 107.2.1] 2. Note on the cover of the drawings that special inspection is required for concrete. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. 3. Please revise the applicable codes for this project to the 2018 International Codes as adopted by the City of Tucson. The 2024 codes indicated are not what the City of Tucson has currently adopted. 4. Please clarify if the building is equipped with an existing fire sprinkler and fire alarm system. If it is, please be sure to indicate on the cover sheet that the modification of the existing systems will be submitted as a separate permit (not deferred submittal). STRUCTURAL COMMENTS General 1. Please provide the structural calculations for the structural design. Sheet S1.00 1. Please submit the shop drawings for the proposed wood I-joists that indicate both joist end connections. If this is intended to be a deferred submittal, please be sure to list the wood I-joists as a deferred submittal on the cover page of the plans and include the following notes: PER IBC Section 107.3.4 <Name of Registrant>, the registered design professional in charge shall be responsible for reviewing and coordinating submittal documents prepared by others, including phased and deferred submittal items, for compatibility with the design of the building. PER IBC Section 107.3.4.1 Submittal documents for deferred submittal items shall be submitted to the registered design professional in responsible charge, who shall review them and forward them to the Building Official with a notation indicating that the deferred submittal documents have been reviewed and that they have been found to be in general conformance with the design of the building. MECHANICAL COMMENTS 1. Please provide updated outside air mechanical calculations. [Ref. IMC 2018 Sec. 403.2] PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS Sheet E1.01 1. Please provide the MRI equipment supplier drawings as referenced in the electrical plan. 2. Please provide an updated interior lighting energy conservation compliance report for the remodeled space. [Ref. IECC 2018 Sec. 405.3] Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 08/12/2025 | Commercial Mechanical | REQUIRES RESUBMIT | August 12, 2025 1st Review Trident Building Solutions, Inc. Attn: Susan Rancifer 8215 Roswell Road, Bldg. 100 Atlanta, Georgia 30350 Re: RADIOLOGY LTD – CAMP LOWELL TENANT IMROVEMENT City of Tucson Permit Number: TC-COM-0825-01447 Stantec Project Number: 185215066 Stantec File Number: TUC-25-083 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms N/A N/A 956 N/A N/A N/A Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: Concrete. ARCHITECTURAL COMMENTS Sheet A0.00 1. Please provide a complete code analysis for the project. The code analysis should include the Occupancy Group for the existing building, construction type, occupant load, if existing fire sprinklers/alarms are installed, etc. [Ref. IBC 2018 Sec. 107.2.1] 2. Note on the cover of the drawings that special inspection is required for concrete. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. 3. Please revise the applicable codes for this project to the 2018 International Codes as adopted by the City of Tucson. The 2024 codes indicated are not what the City of Tucson has currently adopted. 4. Please clarify if the building is equipped with an existing fire sprinkler and fire alarm system. If it is, please be sure to indicate on the cover sheet that the modification of the existing systems will be submitted as a separate permit (not deferred submittal). STRUCTURAL COMMENTS General 1. Please provide the structural calculations for the structural design. Sheet S1.00 1. Please submit the shop drawings for the proposed wood I-joists that indicate both joist end connections. If this is intended to be a deferred submittal, please be sure to list the wood I-joists as a deferred submittal on the cover page of the plans and include the following notes: PER IBC Section 107.3.4 <Name of Registrant>, the registered design professional in charge shall be responsible for reviewing and coordinating submittal documents prepared by others, including phased and deferred submittal items, for compatibility with the design of the building. PER IBC Section 107.3.4.1 Submittal documents for deferred submittal items shall be submitted to the registered design professional in responsible charge, who shall review them and forward them to the Building Official with a notation indicating that the deferred submittal documents have been reviewed and that they have been found to be in general conformance with the design of the building. MECHANICAL COMMENTS 1. Please provide updated outside air mechanical calculations. [Ref. IMC 2018 Sec. 403.2] PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS Sheet E1.01 1. Please provide the MRI equipment supplier drawings as referenced in the electrical plan. 2. Please provide an updated interior lighting energy conservation compliance report for the remodeled space. [Ref. IECC 2018 Sec. 405.3] Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 08/12/2025 | Commercial Plumbing | REQUIRES RESUBMIT | August 12, 2025 1st Review Trident Building Solutions, Inc. Attn: Susan Rancifer 8215 Roswell Road, Bldg. 100 Atlanta, Georgia 30350 Re: RADIOLOGY LTD – CAMP LOWELL TENANT IMROVEMENT City of Tucson Permit Number: TC-COM-0825-01447 Stantec Project Number: 185215066 Stantec File Number: TUC-25-083 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms N/A N/A 956 N/A N/A N/A Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: Concrete. ARCHITECTURAL COMMENTS Sheet A0.00 1. Please provide a complete code analysis for the project. The code analysis should include the Occupancy Group for the existing building, construction type, occupant load, if existing fire sprinklers/alarms are installed, etc. [Ref. IBC 2018 Sec. 107.2.1] 2. Note on the cover of the drawings that special inspection is required for concrete. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. 3. Please revise the applicable codes for this project to the 2018 International Codes as adopted by the City of Tucson. The 2024 codes indicated are not what the City of Tucson has currently adopted. 4. Please clarify if the building is equipped with an existing fire sprinkler and fire alarm system. If it is, please be sure to indicate on the cover sheet that the modification of the existing systems will be submitted as a separate permit (not deferred submittal). STRUCTURAL COMMENTS General 1. Please provide the structural calculations for the structural design. Sheet S1.00 1. Please submit the shop drawings for the proposed wood I-joists that indicate both joist end connections. If this is intended to be a deferred submittal, please be sure to list the wood I-joists as a deferred submittal on the cover page of the plans and include the following notes: PER IBC Section 107.3.4 <Name of Registrant>, the registered design professional in charge shall be responsible for reviewing and coordinating submittal documents prepared by others, including phased and deferred submittal items, for compatibility with the design of the building. PER IBC Section 107.3.4.1 Submittal documents for deferred submittal items shall be submitted to the registered design professional in responsible charge, who shall review them and forward them to the Building Official with a notation indicating that the deferred submittal documents have been reviewed and that they have been found to be in general conformance with the design of the building. MECHANICAL COMMENTS 1. Please provide updated outside air mechanical calculations. [Ref. IMC 2018 Sec. 403.2] PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS Sheet E1.01 1. Please provide the MRI equipment supplier drawings as referenced in the electrical plan. 2. Please provide an updated interior lighting energy conservation compliance report for the remodeled space. [Ref. IECC 2018 Sec. 405.3] Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 08/13/2025 | Fire New Construction | REQUIRES RESUBMIT | Resolve Stantec comments. Questions: patricia.shelton@tucsonaz.gov |
||
| 08/01/2025 | PDSD Application Completeness Express | REVIEW COMPLETED | |||
| 08/18/2025 | Water - PDSD | REVIEW COMPLETED |