Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0824-01703
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/09/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/09/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Ref; Plan sheet E0.1. The site plan shows 2 ‘SES-A’s at different locations. See KEY NOTE #2. Please clarify. 2 Provide for a common Grounding Electrode System for the services per NEC art 205.58. 3 Indicate addresses for all services and correlate with the electrical site plan. 4 Ref; Plan Sheet E1.0 and E0.1. For clarity, identify the building and SES shown in the power plan KEY NOTE #1 and correlate with the Site Electrical Plan. 5 Please explain why the third 200 amp electrical service is required. Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |
||
| 09/03/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |