Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/09/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Ref; Plan sheet E0.1. The site plan shows 2 ‘SES-A’s at different locations. See KEY NOTE #2. Please clarify.

2 Provide for a common Grounding Electrode System for the services per NEC art 205.58.

3 Indicate addresses for all services and correlate with the electrical site plan.

4 Ref; Plan Sheet E1.0 and E0.1. For clarity, identify the building and SES shown in the power plan KEY NOTE #1 and correlate with the Site Electrical Plan.

5 Please explain why the third 200 amp electrical service is required.

Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements