Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0824-01682
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/17/2024 | Commercial Electrical | APPROVED | |||
09/17/2024 | Commercial Plumbing | APPROVED | |||
09/11/2024 | Site Zoning | APPROVED | |||
09/16/2024 | Water - PDSD | APPROVED | |||
09/16/2024 | Site Engineering | NOT REQUIRED | |||
09/17/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
09/17/2024 | Commercial Building | REQUIRES RESUBMIT | Sheet A0.0, 2018 IBC [P] 2902.2 Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. Occupancy proposed as a B and occupant load exceeds 25. Provide separate facilities for each sex. DMA | ||
09/17/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Sheet A3.0, 2018 IBC Ch 16; Provide supporting structural calculations for new mechanical units supported by roof structure. DMA | ||
09/09/2024 | Fire New Construction | REVIEW COMPLETED | |||
08/30/2024 | PDSD Application Completeness | REVIEW COMPLETED |