Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0824-01669
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/06/2024 | Fire New Construction | NOT REQUIRED | |||
09/25/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
09/24/2024 | Commercial Structural | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0824-01669 ADDRESS/PARCEL: (1240 W AJO WY TUCSON, AZ 85713) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter. COMMENTS: 1. Submit an image of the light fixture for light fixture A as well as its specification to include the light source kelvin temperature and the lumens output. 2. Submit the Outdoor Lighting Code 3. Detail 3/D1 - dimension from the handrail to the stair tread nosing is unclear. Ensure that it is between 34” and 38”. Indicate this on the drawing complying to IBC 1014.2 4. Detail 3/D1 – Handrail shall extend horizontal not less than 12 inches beyond the top riser and continue to slope for the depth of one tread beyond the bottom riser per IBC 1014.6 5. Please resubmit. |
||
08/29/2024 | PDSD Application Completeness | REVIEW COMPLETED |