Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0824-01637
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/05/2024 | Site Zoning | APPROVED | |||
09/09/2024 | Water - PDSD | APPROVED | |||
09/09/2024 | Site Engineering | NOT REQUIRED | |||
09/09/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
09/06/2024 | Commercial Building | REQUIRES RESUBMIT | Sheet A0.0 For questions in regards to plan review comments, please contact Bill McClellan by email at bmcclellan@willdan.com or cell (928)580-3179. All applicable comments followed by the initials (BM) | ||
09/06/2024 | Commercial Electrical | REQUIRES RESUBMIT | Sheet E2.0 Identify existing or new exterior egress EM light fixture to comply with 2018 IBC 1008.3.1 (BM) | ||
09/06/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Sheet A3.0 Mechanical notes listed above, provide structural notes on plan set for review and installation. Incomplete. 2018 IBC 107.2.1 (BM) | ||
09/06/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Sheet P1.0 Provide for review a detail and notes for water heater to be provided with a pan and drain to an approved location per IPC 504.7 -504.7.2 (BM) | ||
09/09/2024 | Fire New Construction | REVIEW COMPLETED | |||
08/22/2024 | PDSD Application Completeness | REVIEW COMPLETED |