Permit Number: TC-COM-0824-01624
Parcel: 12112001B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0824-01624
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2024 Site Zoning APPROVED
09/19/2024 Water - PDSD APPROVED
09/09/2024 Site Engineering NOT REQUIRED
09/19/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
09/05/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Denied
Reason:
Date Completed : 8/31/2024 11:44:21 PM
1. GENERAL - UPDATES: For project updates, please submit sheets with all changes clearly marked in revision clouds.
Please provide a written response to each comment; updates without a clear response to all comments may not be reviewed. If you have any questions regarding the comments, you may contact me directly. Updates may result in additional comments.
2. GENERAL - SPECIAL INSPECTIONS: Detail 2/S2.01 indicates that Special Inspections of the soil conditions are required on this project. Please have the Registered Design Professional in Responsible Charge of this project
complete and return the City of Tucson Special Inspections Certificate with signatures. The form can be downloaded at: https://www.tucsonaz.gov/files/sharedassets/public/city-services/planning-developmentservices/documents/special_inspection_certificate.pdf
3. S1.01 - COLUMN LOCATION: The concrete spread footing below rooftop mechanical unit "RTU-1" is not currently shown centered on the HSS round post. Please confirm that this was intentional and that the foundation has been
designed for eccentric loading.
4. S1.10 - RTU LOCATIONS: Please confirm the final placement of rooftop mechanical units "RTU-2" and "RTU-3". The Mechanical Roof New Work Plan, M2.02, indicates that these units shall be located south of Gridline 4 and 2, respectively. This conflicts with the structural Roof and Foundation Plans. Please coordinate final RTU support between disciplines and resubmit.
5. S1.01 - DESIGN ASSUMPTIONS: The 2018 International Building Code, Section 1603 lists all design information that must be included in the construction documents. Information on the wind and seismic design has been provided in the
structural general notes, Sheet S1.01. However, it is recommended that the Roof Live Load used for the evaluation of the existing structure be provided in the general notes in addition to appearing in the Structural Calculations, Page 2 of
42.






Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Approved
Reason:
Date Completed : 8/24/2024 10:28:56 PM







Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 9/3/2024 5:31:32 PM
1. General - Provide Heat Load calculations. Include O/A in the Calculations. - 2015 IECC Section C403.2.1 Calculation
of heating and cooling loads.
2. Plan Sheet M0.02 - Provide on the RTU Schedule Total BTUH, Sensible BTUH, and Latent BTUH. Al values must
meet COMcheck Mechanical Compliance Certificate submitted and Heat Load Calculations. - 2015 IECC Section
C103.2Information on construction documents - 2018 IBC – Section [A]107.2.1Information on construction documents.
3. Plan Sheet M2.02 - If applicable. Provide clear dimensions from all serviceable equipment to the edge of building on
roof. (RTU #3, DSCU 1, DSCU-2) - 2018 IMC Section [BE] 304.11 Guards.







Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 8/29/2024 10:32:56 AM






Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 9/5/2024 12:09:51 PM
First Plumbing Review:
1). PLAN PAGE P3.01: Drinking fountain symbol in wrong location on both riser diagrams. Correctly Identify the Drinking
fountain location. -2018 IPC 106.3.1
09/19/2024 Fire New Construction REVIEW COMPLETED
08/21/2024 PDSD Application Completeness REVIEW COMPLETED