Permit Number: TC-COM-0824-01603
Parcel: 14005032J

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0824-01603
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2024 Commercial Structural APPROVED
08/30/2024 Site Engineering APPROVED Any disturbance to the basin must be remediated.
08/28/2024 Site Zoning NOT REQUIRED
08/30/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
08/29/2024 Commercial Mechanical REQUIRES RESUBMIT 1. A 10” x 10” metal grille does not have a net open area of 100 square inches. Check with the manufacturer for the net open area (typically about 75%). [Initial comment: Show how the dryer installation complies with Section 504.6, IMC 2018.]
2. Comment not addressed. [Initial comment: Provide signage indicating the total equivalent length of the concealed dryer exhaust duct. Reference: Section 504.8.4.2, IMC 2018.]
08/29/2024 Commercial Plumbing REQUIRES RESUBMIT 1. PEX water size table has not been corrected to limit the water velocity to a maximum of 8 feet per second. See Plumbing Keynote #8/P2. [Initial comment: Revise the Water Pipe Sizing Table on sheet P2 to limit the water velocity in PEX tubing to a maximum of 8 feet per second (see Keynote 8). Reference: Section 303.2, IPC 2018.]
2. Coordinate the water service to the units as shown on P1 and P2. [Initial comment: Sheet P1 shows each dwelling unit with a ¾” water service but sheet P2 shows a 1” water service to each dwelling unit. With a demand of 16 GPM (Tables E103.3(2) and E103.3(3), IPC 2018), a 1-1/4” service is required to keep the water velocity below 8 feet per second. Reference: Section 303.2, IPC 2018.]
3. Comment not addressed. [Initial comment: Clarify how the grey water drain pipe and the T&P relief pipe, both located above the floor slab, can cross open doorways. Reference: Section 1078.2.1, IBC 2018.]
4. Comment not addressed. [Initial comment: Provide waste and vent isometrics to clarify the design of the sanitary drain system (e.g. unexplained dead end drains in units 1 and 2; unconnected and missing vent piping, etc.). Reference: Section 107.2.1, IBC 2018.]
08/16/2024 PDSD Application Completeness REVIEW COMPLETED