Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0824-01600
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/16/2024 | Commercial Electrical | APPROVED | |||
| 09/16/2024 | Commercial Structural | APPROVED | Please NOTE: we are approving this portion of the project, however there are 2 suites involved, a second permit has been created for suite 108. Please do make sure to complete the process for both permits. | ||
| 09/13/2024 | Site Engineering | APPROVED | |||
| 09/11/2024 | Site Zoning | APPROVED | |||
| 09/16/2024 | Commercial Plumbing | NOT REQUIRED | |||
| 09/16/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/16/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2018 | ||
| 08/26/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 08/15/2024 | PDSD Application Completeness Express | REVIEW COMPLETED | It appears the permit documents uploaded lists multiple addresses and each individual address requires its own permit. This permit is for the identified main address 5650 S 12TH AV Unit: UNIT 100 only. Please start new permit application for all other addresses. |