Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2024 Commercial Electrical APPROVED
09/16/2024 Commercial Structural APPROVED Please NOTE: we are approving this portion of the project, however there are 2 suites involved, a second permit has been created for suite 108. Please do make sure to complete the process for both permits.
09/13/2024 Site Engineering APPROVED
09/11/2024 Site Zoning APPROVED
09/16/2024 Commercial Plumbing NOT REQUIRED
09/16/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/16/2024 Commercial Mechanical REQUIRES RESUBMIT Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2018
08/26/2024 Fire New Construction REVIEW COMPLETED
08/15/2024 PDSD Application Completeness Express REVIEW COMPLETED It appears the permit documents uploaded lists multiple addresses and each individual address requires its own permit. This permit is for the identified main address 5650 S 12TH AV Unit: UNIT 100 only. Please start new permit application for all other addresses.