Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0824-01585
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/10/2024 | Site Zoning | APPROVED | |||
09/16/2024 | Water - PDSD | APPROVED | |||
09/13/2024 | Commercial Plumbing | NOT REQUIRED | |||
09/12/2024 | Site Engineering | NOT REQUIRED | |||
09/16/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
09/13/2024 | Commercial Electrical | REQUIRES RESUBMIT | Sheet E1, 2018 IBC Ch 10; Provide exit signs and illumination details on plans. DMA | ||
09/13/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Sheet A1, 2018 IMC; 506.1 General. Commercial kitchen hood ventilation ducts and exhaust equipment shall comply with the requirements of this section. Commercial kitchen grease ducts shall be designed for the type of cooking appliance and hood served. Provide an engineered design for kitchen. DMA | ||
09/13/2024 | Commercial Structural | REQUIRES RESUBMIT | Sheet A1; For questions regarding Plan Review comments please contact: Dino M. Accardo, MCP, CBO, E: daccardo@willdan.com. Fire Plan Review is NOT within the scope of this review. All applicable comments will be followed with the initials, DMA. 1. Sheet A1, 2018 IBC Table 2902.1; Fixture calc does not take into account required lavs. DMA 2. Sheet A3, 2018 IBC 1010.1.2.1 Direction of swing. Pivot or side-hinged swinging doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons. DMA 3. Sheet A3, 2018 IBC 1007.1.1 Two exits or exit access doorways. Where two exits, exit access doorways, exit access stairways or ramps, or any combination thereof, are required from any portion of the exit access, they shall be placed a distance apart equal to not less than one-half of the length of the maximum overall diagonal dimension of the building or area to be served measured in a straight line between them. The door swing for the private dining area must swing out based upon the occupant load of the space. This will also negate this egress path and exit from other spaces of the dining areas due to those occupant loads exceeding 50 or more. DMA 4. Sheet A3, 2018 IBC 1029.13 Aisle accessways. Aisle accessways for seating at tables shall comply with Section 1029.13.1. Aisle accessways for seating in rows shall comply with Section 1029.13.2. Dimension the plans to demonstrate compliance. DMA |
||
09/06/2024 | Fire New Construction | REQUIRES RESUBMIT | OL is >299. Building fire alarm with notification is required. IFC 907.2.1. Verify there is a fire alarm and include in the code review. Thank you. john.vincent@tucsonaz.gov 5203495581 |
||