Permit Number: TC-COM-0824-01585
Parcel: 105097390

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0824-01585
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2024 Site Zoning APPROVED
09/16/2024 Water - PDSD APPROVED
09/13/2024 Commercial Plumbing NOT REQUIRED
09/12/2024 Site Engineering NOT REQUIRED
09/16/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
09/13/2024 Commercial Electrical REQUIRES RESUBMIT Sheet E1, 2018 IBC Ch 10; Provide exit signs and illumination details on plans. DMA
09/13/2024 Commercial Mechanical REQUIRES RESUBMIT Sheet A1, 2018 IMC; 506.1 General. Commercial kitchen hood ventilation ducts and exhaust equipment shall comply with the requirements of this section. Commercial kitchen grease ducts shall be designed for the type of cooking appliance and hood served. Provide an engineered design for kitchen. DMA
09/13/2024 Commercial Structural REQUIRES RESUBMIT Sheet A1; For questions regarding Plan Review comments please contact: Dino M. Accardo, MCP, CBO, E: daccardo@willdan.com. Fire Plan Review is NOT within the scope of this review. All applicable comments will be followed with the initials, DMA.

1. Sheet A1, 2018 IBC Table 2902.1; Fixture calc does not take into account required lavs. DMA
2. Sheet A3, 2018 IBC 1010.1.2.1 Direction of swing. Pivot or side-hinged swinging doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons. DMA
3. Sheet A3, 2018 IBC 1007.1.1 Two exits or exit access doorways. Where two exits, exit access doorways, exit access stairways or ramps, or any combination thereof, are required from any portion of the exit access, they shall be placed a distance apart equal to not less than one-half of the length of the maximum overall diagonal dimension of the building or area to be served measured in a straight line between them. The door swing for the private dining area must swing out based upon the occupant load of the space. This will also negate this egress path and exit from other spaces of the dining areas due to those occupant loads exceeding 50 or more. DMA
4. Sheet A3, 2018 IBC 1029.13 Aisle accessways. Aisle accessways for seating at tables shall comply with Section 1029.13.1. Aisle accessways for seating in rows shall comply with Section 1029.13.2. Dimension the plans to demonstrate compliance. DMA
09/06/2024 Fire New Construction REQUIRES RESUBMIT OL is >299. Building fire alarm with notification is required. IFC 907.2.1. Verify there is a fire alarm and include in the code review. Thank you.
john.vincent@tucsonaz.gov
5203495581
08/14/2024 PDSD Application Completeness REVIEW COMPLETED