Permit Number: TC-COM-0824-01550
Parcel: 126190840

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0824-01550
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2024 Site Zoning APPROVED
09/10/2024 Site Engineering NOT REQUIRED
09/13/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/13/2024 Commercial Electrical REQUIRES RESUBMIT Sheet A1, 2018 IBC [A]107.2.1 Information on construction documents. Construction documents shall be of sufficient clarity to indicate the location, nature and extent of the work proposed and show in detail that it will conform to the provisions of this code and relevant laws, ordinances, rules and regulations, as determined by the building official. Provide existing structure Building Data and existing occupancy classification. No MEPS were provided DMA
09/13/2024 Commercial Mechanical REQUIRES RESUBMIT Sheet A1, 2018 IBC [A]107.2.1 Information on construction documents. Construction documents shall be of sufficient clarity to indicate the location, nature and extent of the work proposed and show in detail that it will conform to the provisions of this code and relevant laws, ordinances, rules and regulations, as determined by the building official. Provide existing structure Building Data and existing occupancy classification. No MEPS were provided DMA
09/13/2024 Commercial Plumbing REQUIRES RESUBMIT Sheet A1; For questions regarding Plan Review comments please contact: Dino M. Accardo, MCP, CBO, E: daccardo@willdan.com. Fire Plan Review is NOT within the scope of this review. All applicable comments will be followed with the initials, DMA.

Sheet A1, 2018 IBC [A]107.2.1 Information on construction documents. Construction documents shall be of sufficient clarity to indicate the location, nature and extent of the work proposed and show in detail that it will conform to the provisions of this code and relevant laws, ordinances, rules and regulations, as determined by the building official. Provide existing structure Building Data and existing occupancy classification. No MEPS were provided DMA
09/03/2024 Commercial Structural REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0824-01550
ADDRESS/PARCEL: (815 S COLUMBUS BL TUCSON, AZ 85711)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.
COMMENTS:
1. Submit a complete Means of Egress Plan to include all the routes along with their distances and at each exit, enumerate the total distances, exit width required/exit width provided and the number of occupants exiting.
2. Please complete the Building Code/Zoning Code Analysis.
a. NOTE: We understand you have selected R-4 (please specify exactly how many clients you will have).
b. The chosen use is Behavioral Health (please respond that your selection confirms what you selected from the City Zoning Code & your State Department of Health Services License Application). With R-4 your clients will reside at the facility on a 24-hour basis.
c. Please provide a description of the services that you provide (a description of your daily operation written down to include the type of clients/patients, the type of services, the professionals who will be providing the services, etc).
d. Include a statement as part of your code analysis as to how the facility handles any persons receiving custodial care who require limited verbal or physical assistance responding to an emergency situation to complete building evacuation and self preservation. Specify Condition 1 or Condition 2 per IBC 310 (this will determine the type of fire sprinkler system the fire department will require).
3. On the Site Plan show/indicate the Accessible route from drop off location to the accessible entry door complying to IBC 106 & ANSI A117. In an Emergency, show/locate the gathering area/dispersal area where it is safe from danger minimum 50 ft away from structure per IBC 310.5 and 1028.5.
4. Indicate the clear opening of the doors complying to ANSI A117.
5. Indicate the clear width of hallways.
6. Show/locate the side & back grab bars at the Water Closet as well as at the Shower, make sure to indicate the installation of Structural Backer Board for these grab bars per IBC Chapter 11.
7. Provide Emergency Escape & Rescue Openings per R310 at every bedroom/sleeping space. On the drawing adjacent to the opening(s), indicate the clear opening for both horizontally and vertically and provide the dimension from the finish floor to the bottom of the opening. Indicate if there are obstacles on either side of the opening.
8. Fire Sprinkler is required per IBC 420 and processed as a separate permit. Submit the drawings to Tucson Fire Department for review and approval. They will conduct fire inspection, the inspection approval document will be required as a deferred submittal before issuing the Certificate of Occupancy.
9. A fire alarm is required [IBC 907], If they exist...indicate them on your drawing. If not...please how this is addressed.
10. Illumination with emergency backup power is required in all components of the means of egress system [IBC 1008]. Please locate/identify/label those equipments including the Lighted Exit Sign(s), Emergency Light(s) w/ battery backup, Fire/Audible/Smoke Alarms if applicable, Fire Extinguisher on your plan (to be inspected by Tucson Fire Department).
11. Electrical work (conductors/wiring/breaker ONLY) related to the installation will be inspected by City of Tucson inspectors, show on your plans so that our inspectors will know what wiring/breaker to inspect and shall also be reviewed as part of this permit.
12. Any new work must be included as part of this building permit.
14. An Operator's License must be applied for with the State, the absence of this license shall void this building permit.
15. Submit a draft copy of the State Department of Health Services License application confirming the exact use we will enter in the certificate of occupancy document.
16. Please be consistent with the square footage of the dwelling. You show 2,075 and 2,863 sf. While the Assessor show 1,621 sf. Please correct this.
17. The Assessor still categorize Bedroom 1 as a carport and may not have a permit. The front patio and the back patio looks to be additions that do not have building permit. Please provide documentation that every portion of this structure are all permitted. If this is not the case, please submit a complete set of drawings for every part of this dwelling that is not permitted.
18. Please resubmit.
08/27/2024 Fire New Construction REQUIRES RESUBMIT Please provide condition for all residents for the R4 Occupancy designation on the plan set.
Questions: patricia.shelton@tucsonaz.gov
08/09/2024 PDSD Application Completeness Express REVIEW COMPLETED