Permit Number: TC-COM-0824-01548
Parcel: 10711092A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0824-01548
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2024 Commercial Mechanical APPROVED
08/22/2024 Commercial Plumbing APPROVED
08/20/2024 Site Zoning APPROVED
08/21/2024 Water - PDSD APPROVED
08/26/2024 Site Engineering NOT REQUIRED
08/26/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/22/2024 Commercial Building REQUIRES RESUBMIT Sheet TS1; For questions regarding Plan Review comments please contact: Dino M. Accardo, MCP, CBO, E: daccardo@willdan.com. Fire Plan Review is NOT within the scope of this review. All applicable comments will be followed with the initials, DMA.

1. Sheet TS1, 2018 IBC 508.1 General. Each portion of a building shall be individually classified in accordance with Section 302.1. Where a building contains more than one occupancy group, the building or portion thereof shall comply with the applicable provisions of Section 508.2, 508.3 or 508.4, or a combination of these sections. Identify in Building Data original existing building design. If mixed -use separated (structure is non-sprinklered) provide listing and demising wall details. DMA
2. Sheet A1, 2009 A117.1 608.2.2.3 Seat. A folding seat complying with Section 610 shall be provided on an end wall for roll-in shower. DMA
08/21/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.
Please provide a complete panel schedule for panel 'M'.
Ref; 2018 IBC section 107.2.1, 2018 NEC art 408.4.
08/22/2024 Fire New Construction REVIEW COMPLETED
08/08/2024 PDSD Application Completeness Express REVIEW COMPLETED