Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0824-01516
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/19/2024 | Site Zoning | APPROVED | |||
| 08/20/2024 | Water - PDSD | APPROVED | |||
| 08/21/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/21/2024 | Commercial Building | REQUIRES RESUBMIT | For questions in regards to plan review comments, please contact Bill McClellan by email at bmcclellan@willdan.com or cell (928)580-3179. All applicable comments to be followed by the initials (BM) 1. Cover Sheet Cover sheet should also have registrants seal on sheet per 2018 IBC 107.1 (BM) 2. Sheet x1.1 Plan identifies two exits. Provide travel distance for both exits on exiting plan per 2018 1017.2 (BM) 3. Sheet x1.1 Hi / Low Drinking fountain is required by per 2018 IBC table 2902.1, 2018 IPC 410.3 requires a High and low drinking fountain for wheel chair use. City of Tucson IPC amendment to 410.4 for substitutions, states when a single drinking fountain is required, it may be substituted with a point of use water cooler or dispenser. (BM) 4. Sheet a1 Minimum clear door opening width at mail room should be 32" per 2018 IBC1010.1.1 (BM) 5. Sheet a6 Walls and partitions within 2' of water closets and service sinks shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4' above finished floor. 2018 IBC 1209.2.2 |
||
| 08/21/2024 | Commercial Electrical | REQUIRES RESUBMIT | Sheet E2 Provide for review a light fixture schedule to include different types of fixture, electrical data and EM and battery requirements. Incomplete 2018 IBC 107.2.1 (BM) | ||
| 08/21/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Sheet m1 Provide for review, mechanical compliance certificate for mechanical system to comply with 2018 IECC C403 (BM) Incomplete | ||
| 08/21/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Sheet p3 Wall box identified for ice maker will require an WHA where a quick-closing valve utilized. 2018 IPC 604.9 (BM) | ||
| 08/21/2024 | Site Engineering | REQUIRES RESUBMIT | This project is within a regulated floodplain and requires a Floodplain Use Permit (FUP.) Please start a new FUP at our permit application web page: https://tdc-online.tucsonaz.gov/#/home NOTE: Documentation of a cost estimate from your contractor will be required if this project involves any reconstruction, repair, rehabilitation, structurally connected addition, or other improvement of an existing structure (including TIs and solar). Construction of separate builds/new structures does not require a cost estimate to be provided. Construction of new buildings require elevation one foot above the base flood elevation, which may require that the foundation of the building be raised as much as two feet above the existing elevation onsite. Storage buildings with no utilities may be wet floodproofed using flood vents. For all new construction buildings, two elevation certificates must be filled out by a registered land surveyor and submitted to the City, one before the foundation is poured and one after construction is completed. Instructions: 1. Navigate into the current project in the “My Work” tab. Within the permit, navigate to the “Sub-Records” tab and click “Apply” on the Floodplain Use Permit Sub-Record 2. Locations -> Confirm the location is accurate to the project. Click “Next” 3. Type -> Fill in the “Square Feet” and “Valuation” boxes with the project area and a contractor-provided cost estimate (See note above: for new structures, input 0). Click “Next” 4. Contacts -> Confirm contacts and add any additional contacts if applicable. Click “Next” 5. More Info -> This will be filled in by the engineer assigned to your case, Click “Next” 6. Attachments -> Please attach the project plan, supporting documentation for the cost estimate (if applicable), and a drainage/hydrology report (if applicable). Click “Next” 7. Signature -> Read the statement and type your name. Sign your name below (You may Enable Type Signature to have the software sign for you.) Click “Next” 8. Review and Submit -> Review all information to ensure accuracy. Click “Submit” Ryan Insalaco Engineering Associate City of Tucson Planning & Development Services Department Email: ryan.insalaco@tucsonaz.gov |
||
| 08/19/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 08/06/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |