Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0824-01493
Parcel: 10606013B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0824-01493
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/28/2024 Commercial Structural REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter to address each of the comments indicating how the Building Review comments were addressed. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.
1. Please amend plans to indicate the ages of the children that will be attending the facility. IBC 107.2.1
Please note: Group E, day care facilities include buildings and structures or portions thereof occupied by more than five children older than 21/2 years of age who receive educational, supervision or personal care services for fewer than 24 hours per day.
Group E Day care occupancies include facilities intended to be used for the care and supervision of more than five children older than 21/2 years of age where individual care is for a period of less than 24 hours per day.
Day care centers are a special concern since they are generally occupied by preschool children who are less capable of responding to an emergency. The hazards found in a day care center are far greater than in normal educational facilities, not so much because of the occupant or fuel load, but because of the inability of the occupants to respond.
Children 21/2 years of age or less usually are not able to recognize an emergency situation, may not respond appropriately or simply may not be able to egress without assistance. Thus, facilities that have more than five children 21/2 years of age or less are classified as child care facilities and considered to be Group I-4 (see Section 308.6) unless the provisions of Sections 308.6.1 through 308.6.4 allow for a different classification.
Locations where child care may be provided that would not be considered Group E or I-2 are addressed in Sections 305.2.1 through 305.2.3.
2. Please ensure the door from closet 11A does not encroach into the required means of egress width. IBC 1005.7 For example, provide a dimension on the plan to indicate to width from the edge of door to the wall .
3. Please amend plans to show the accessibility features required by IEBC 305.4.2 as follows:
A. Where an entire building undergoes a change of occupancy, it shall comply with Section 305.4.1 and shall have all of the following accessible features:
1.Not fewer than one accessible building entrance.
2.Not fewer than one accessible route from an accessible building entrance to primary function areas.
3.Signage complying with Section 1111 of the International Building Code.
4.Accessible parking, where parking is being provided.
5.Not fewer than one accessible passenger loading zone, where loading zones are provided.
6.Not fewer than one accessible route connecting accessible parking and accessible passenger loading zones to an accessible entrance.
B. Where a building undergoes a partial change of occupancy, such as where there is a tenant change or a change in function of a specific area, then the level of accessibility provided must achieve the same level as if that space were undergoing an alteration. Basically, the intent is that any spaces or elements being altered will meet new accessibility provisions unless technically infeasible (see Section 305.6). If the area changing occupancy is a primary function of the space, an evaluation of the accessible route, as well as bathrooms and drinking fountains serving this space, must be made. If these elements are not accessible, improvements must be made. There is a limit, however, to the cost of the additional improvements to a maximum of 20 percent of the cost of the alteration (see Section 305.7). The reference to Section 305.8 provides for additional allowances because the designer or owner is still dealing with existing building constraints IEBC 305.4.1

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
08/27/2024 Fire New Construction REQUIRES RESUBMIT -Indicate whether the building has a building fire alarm that is a voice/alarm per IFC 2018, 907.2.3
-Verify the building does not have a fire sprinkler system. Your code review states non sprinklered, however, google maps image shows what appears to be a fire sprinkler bell on the front of the building.
john.vincent@tucsonaz.gov
5203495581
09/03/2024 Site Engineering REQUIRES RESUBMIT 1. See zoning comments
08/29/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0824-01493
3902 N FLOWING WELLS RD. – C-1
C of O Daycare (1st Review)

TRANSMITTAL: August 29, 2024

Resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-1 zone (UDC 4.7.20). Daycare is a allowed use in the zone (UDC Table 4.8-4), subject to Use Specific Standard 4.9.13.O.

1. The (E) STORAGE, (E) AWNING & (E) CANOPY show up on aerial photos some time after 2008. Zoning was not able to find approved permit/compliance documents for these structures. One of three things will need to happen: 1) Provide approved permit/compliance documents. 2) Show the structures to be removed. 3) Include the structures in this permit. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/02/2024 PDSD Application Completeness Express REVIEW COMPLETED