Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0824-01488
Parcel: 111063620

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0824-01488
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/05/2024 Commercial Mechanical APPROVED MASTER SET LOCATED AT: TC-COM-0824-01488 (3220 E MONTE VISTA DR Unit:UNIT G TUCSON, AZ 85716) WITH REVIEWS TO BE PERFORMED ON TC-COM-0824-01489 (3220 E MONTE VISTA DR Unit:UNIT H TUCSON, AZ 85716), TC-COM-0824-01490 (3220 E MONTE VISTA DR Unit:UNIT I TUCSON, AZ 85716, TC-COM-0824-01491 (3220 E MONTE VISTA DR Unit:UNIT J TUCSON, AZ 85716
09/05/2024 Commercial Plumbing APPROVED MASTER SET LOCATED AT: TC-COM-0824-01488 (3220 E MONTE VISTA DR Unit:UNIT G TUCSON, AZ 85716) WITH REVIEWS TO BE PERFORMED ON TC-COM-0824-01489 (3220 E MONTE VISTA DR Unit:UNIT H TUCSON, AZ 85716), TC-COM-0824-01490 (3220 E MONTE VISTA DR Unit:UNIT I TUCSON, AZ 85716, TC-COM-0824-01491 (3220 E MONTE VISTA DR Unit:UNIT J TUCSON, AZ 85716
08/27/2024 Commercial Structural APPROVED MASTER SET LOCATED AT: TC-COM-0824-01488 (3220 E MONTE VISTA DR Unit:UNIT G TUCSON, AZ 85716) WITH REVIEWS TO BE PERFORMED ON TC-COM-0824-01489 (3220 E MONTE VISTA DR Unit:UNIT H TUCSON, AZ 85716), TC-COM-0824-01490 (3220 E MONTE VISTA DR Unit:UNIT I TUCSON, AZ 85716, TC-COM-0824-01491 (3220 E MONTE VISTA DR Unit:UNIT J TUCSON, AZ 85716
08/29/2024 Site Zoning APPROVED MASTER SET LOCATED AT: TC-COM-0824-01488 (3220 E MONTE VISTA DR Unit:UNIT G TUCSON, AZ 85716) WITH REVIEWS TO BE PERFORMED ON TC-COM-0824-01489 (3220 E MONTE VISTA DR Unit:UNIT H TUCSON, AZ 85716), TC-COM-0824-01490 (3220 E MONTE VISTA DR Unit:UNIT I TUCSON, AZ 85716, TC-COM-0824-01491 (3220 E MONTE VISTA DR Unit:UNIT J TUCSON, AZ 85716
09/05/2024 Water - PDSD APPROVED MASTER SET LOCATED AT: TC-COM-0824-01488 (3220 E MONTE VISTA DR Unit:UNIT G TUCSON, AZ 85716) WITH REVIEWS TO BE PERFORMED ON TC-COM-0824-01489 (3220 E MONTE VISTA DR Unit:UNIT H TUCSON, AZ 85716), TC-COM-0824-01490 (3220 E MONTE VISTA DR Unit:UNIT I TUCSON, AZ 85716, TC-COM-0824-01491 (3220 E MONTE VISTA DR Unit:UNIT J TUCSON, AZ 85716
09/03/2024 Site Engineering NOT REQUIRED MASTER SET LOCATED AT: TC-COM-0824-01488 (3220 E MONTE VISTA DR Unit:UNIT G TUCSON, AZ 85716) WITH REVIEWS TO BE PERFORMED ON TC-COM-0824-01489 (3220 E MONTE VISTA DR Unit:UNIT H TUCSON, AZ 85716), TC-COM-0824-01490 (3220 E MONTE VISTA DR Unit:UNIT I TUCSON, AZ 85716, TC-COM-0824-01491 (3220 E MONTE VISTA DR Unit:UNIT J TUCSON, AZ 85716
09/05/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT MASTER SET LOCATED AT: TC-COM-0824-01488 (3220 E MONTE VISTA DR Unit:UNIT G TUCSON, AZ 85716) WITH REVIEWS TO BE PERFORMED ON TC-COM-0824-01489 (3220 E MONTE VISTA DR Unit:UNIT H TUCSON, AZ 85716), TC-COM-0824-01490 (3220 E MONTE VISTA DR Unit:UNIT I TUCSON, AZ 85716, TC-COM-0824-01491 (3220 E MONTE VISTA DR Unit:UNIT J TUCSON, AZ 85716
08/29/2024 Commercial Electrical REQUIRES RESUBMIT MASTER SET LOCATED AT: TC-COM-0824-01488 (3220 E MONTE VISTA DR Unit:UNIT G TUCSON, AZ 85716) WITH REVIEWS TO BE PERFORMED ON TC-COM-0824-01489 (3220 E MONTE VISTA DR Unit:UNIT H TUCSON, AZ 85716), TC-COM-0824-01490 (3220 E MONTE VISTA DR Unit:UNIT I TUCSON, AZ 85716, TC-COM-0824-01491 (3220 E MONTE VISTA DR Unit:UNIT J TUCSON, AZ 85716
Please address the electrical plan review comments and provide a written response.

1. Ref; Electrical Line Diagram and associated notes.

1a. The Line Diagram notes call for panels' ‘G’,’H’, and ‘J’ to be fed with a 100A/1P Circuit Breaker and feeder conductor sizes called out as 3#4 AL or 3# 6Cu with #8 ground in new 1-½ “conduit or equivalent SER cable. These feeders are undersized for the OCPD’s protecting them, NEC 310.15(B)(16) Table, 75c column. Please clarify and revise the plans accordingly.

1b. The Line Diagram notes call for the existing panels’ ‘L’ and ‘K’ to be fed with 50A/2P Circuit Breakers as Previously. The ‘TYPICAL TENANT PANEL’ load calculations show a total load of 66 amps. How does this work fed by a 50A/2P Circuit Breaker with a load greater than the rating of the 50A OCPD.. Please clarify. Revise the load calculations as necessary.

2. Provide GFI protected exterior receptacles for each unit as required per NEC art 210.52(E).

3. Provide combination smoke detectors as required per 2018 IBC section 907.2.10.

Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
08/12/2024 Fire New Construction REVIEW COMPLETED MASTER SET LOCATED AT: TC-COM-0824-01488 (3220 E MONTE VISTA DR Unit:UNIT G TUCSON, AZ 85716) WITH REVIEWS TO BE PERFORMED ON TC-COM-0824-01489 (3220 E MONTE VISTA DR Unit:UNIT H TUCSON, AZ 85716), TC-COM-0824-01490 (3220 E MONTE VISTA DR Unit:UNIT I TUCSON, AZ 85716, TC-COM-0824-01491 (3220 E MONTE VISTA DR Unit:UNIT J TUCSON, AZ 85716