Permit Number: TC-COM-0823-02119
Parcel: 12905131E

Address:
2019 E 17TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0823-02119
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/17/2024 Commercial Mechanical APPROVED
04/22/2024 Site Engineering APPROVED
04/18/2024 Site Zoning APPROVED
04/22/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/17/2024 Commercial Plumbing REQUIRES RESUBMIT 1. The invert elevation of the next upstream manhole, shown on sheet P100, does not affect the backwater requirement. Manhole 5597-02 has a rim elevation of 2447.68 feet per the survey data shown on sheet G002. The FFE is not provided but the parcel appears to have an elevation between 2444 and 2445 feet . Re-evaluate the need for a backwater valve. [Initial comment: Provide the rim elevation of the next upstream sanitary manhole and the first-floor elevation. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.]
2. Comment not resolved. The 884.8 square foot roof does not appear to have a secondary scupper. The secondary scupper for the North roof is located at the high point of a cricket. What depth of ponding will be caused by this location of the secondary scupper? Provide structural calculations to show that the roof can safely support the maximum possible water depth caused by ponding if the primary roof drains are assumed to be blocked. Reference: Section 1101.7, IPC 2018. [Initial comment: Provide roof drainage calculations and plans. Provide overflow protection for the roof. Reference: Sections 1101, 1106 and 1108, IPC 2018.]
04/16/2024 Commercial Structural REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0823-02119
ADDRESS/PARCEL: (2019 E 17TH ST TUCSON, AZ 85719)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:
1. Please coordinate/correct the Gross Floor area on the Cover Sheet does not match the square footage when added together shown on sheet G001 under Design Occupant Load.
2. The exterior wall on the west end of the New Outdoor Carport is not present in the Structural, Mechanical, Plumbing and Electrical drawings. Please have this corrected.
3. The wall jog and door is not reflected in the Structural, Mechanical, Plumbing and Electrical drawings. Please have this corrected.
4. Show the required accessible clear area on the floor at the water closet making sure the lavatory does not encroach onto this clear area.
5. Please resubmit.
03/16/2024 PDSD Application Completeness Express REVIEW COMPLETED