Permit Number: TC-COM-0823-02101
Parcel: 10707003D

Address:
1109 W GLENN ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0823-02101
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2024 Site Engineering APPROVED
06/04/2024 Site Zoning APPROVED
06/05/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
05/17/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Denied
Reason:
Date Completed : 5/15/2024 4:20:00 PM
1. GENERAL - UPDATES: For project updates, please submit sheets with all changes clearly marked in revision clouds. Please provide a written response to each comment; updates without a clear response to all comments may not be reviewed. If you have any questions regarding the comments, you may contact me directly. Updates may result in additional comments.

2. S1.1 - MISSING INFORMATION: The structural general notes, Section "Cold-Formed Steel Framing", Notes 2 & 3 clearly identify the minimum yield strength for cold-formed studs and joists when cold-formed members are 12, 14 or 16 gage thickness (-54, -68 and -97 mils). Please update these notes to provide a minimum yield strength for the more common 18 and 20 gage members, bearing in mind that the structural calculation package uses 50 ksi steel for all sizes.

3. S2.2 - CONFLICTING INFORMATION: Structural Sheet S2.2 conflicts with the Architectural Sheet A1.2 regarding the interior cold-formed steel stud walls separating the Open Office 103, Offices 107-110 and the Reception area. Where
Sheet S2.2 calls out a partition wall at the Reception area, no wall occurs on A1.2. Further, A1.2 specifies Wall Type "WL-G" for the north-south partition walls, which conflict in both stud gage and stud spacing with Sheet S2.2, Plan Note 7. Please coordinate the structural and architectural plans to resolve these conflicts.

4. S2.2 - CONFLICTING INFORMATION: The Canopy Framing Plan on S2.2 calls for tube framing by the preengineered metal building manufacturer to support the proposed canopy. Refer to Detail 229 for more information. However, no tube framing appears on the sidewall framing at Frame Lines E or 6 in Metal Building drawings "Mtl Bldg23022R SEALED APPROVALS-HArev_v1.pdf", Pages 9 & 11. Please coordinate with the metal building manufacturer to confirm that proper backing has been provided for the canopy framing.

5. S4.2 - CONFLICTING INFORMATION: Detail 232, Note 2, calls out a beam size that conflicts with the beam schedule on Sheet S2.3 and Detail 231. Please confirm which note will control and resubmit to resolve this conflict.

6. S4.2/S4.3 - MISSING INFORMATION: Details 237 and 240 show a cold-formed steel pony wall supporting the mezzanine roof joists above Steel Beam "B7" along Frame Line E. Please provide a minimum stud size and spacing for this pony wall.

7. Supplemental Calculation Package - ENGINEER'S SEAL: The structural calculations by Babbitt Smith Engineering dated April 29, 2024 were submitted without an engineer's seal. Please resubmit the calculations signed and sealed by a professional engineer licensed in the State of Arizona.


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 5/8/2024 2:49:53 PM


Mechanical N/A

Electrical N/A

Plumbing N/A
Fire N/A




Building Approved

Mechanical N/A

Electrical N/A

Plumbing N/A
05/28/2024 Fire New Construction REVIEW COMPLETED
05/08/2024 PDSD Application Completeness REVIEW COMPLETED