Permit Number: TC-COM-0823-02100
Parcel: 12517032A

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-COM-0823-02100
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/23/2024 Concrete Installation Inspection (Deferred Submittal) Express REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0823-02100
ADDRESS/PARCEL: (3805 E BROADWAY BL TUCSON, AZ 85716)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.
COMMENTS:
1. Please complete the upper portion of the Special Inspection Certificate Form (SECTION: Certificate of Special Inspection by Owner.
2. NOTE: the submitted form is the 2006 version. Please use the year 2018 version (the City of Tucson adopted the 2018 iCodes).
3. You listed Soils, Concrete Testing, Concrete Construction, Masonry & Structural Steel as required special inspections under CATEGORY within the form. However, no field reports were submitted. Per International Building Code section 1704, Inspection Field Reports are to be filed/submitted with the Building Official. Please submit all field reports enumerated on the list.
4. Please resubmit.
10/23/2024 Masonry Inspection (Deferred Submittal) Express REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0823-02100
ADDRESS/PARCEL: (3805 E BROADWAY BL TUCSON, AZ 85716)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.
COMMENTS:
1. Please complete the upper portion of the Special Inspection Certificate Form (SECTION: Certificate of Special Inspection by Owner.
2. NOTE: the submitted form is the 2006 version. Please use the year 2018 version (the City of Tucson adopted the 2018 iCodes).
3. You listed Soils, Concrete Testing, Concrete Construction, Masonry & Structural Steel as required special inspections under CATEGORY within the form. However, no field reports were submitted. Per International Building Code section 1704, Inspection Field Reports are to be filed/submitted with the Building Official. Please submit all field reports enumerated on the list.
4. Please resubmit.
10/23/2024 Other Inspection Reports (Deferred Submittal) Express REQUIRES RESUBMIT STRUCTURAL STEEL

ACTIVITY NO. TC-COM-0823-02100
ADDRESS/PARCEL: (3805 E BROADWAY BL TUCSON, AZ 85716)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.
COMMENTS:
1. Please complete the upper portion of the Special Inspection Certificate Form (SECTION: Certificate of Special Inspection by Owner.
2. NOTE: the submitted form is the 2006 version. Please use the year 2018 version (the City of Tucson adopted the 2018 iCodes).
3. You listed Soils, Concrete Testing, Concrete Construction, Masonry & Structural Steel as required special inspections under CATEGORY within the form. However, no field reports were submitted. Per International Building Code section 1704, Inspection Field Reports are to be filed/submitted with the Building Official. Please submit all field reports enumerated on the list.
4. Please resubmit.
10/23/2024 Site Prep Inspection (Deferred Submittal) Express REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0823-02100
ADDRESS/PARCEL: (3805 E BROADWAY BL TUCSON, AZ 85716)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.
COMMENTS:
1. Please complete the upper portion of the Special Inspection Certificate Form (SECTION: Certificate of Special Inspection by Owner.
2. NOTE: the submitted form is the 2006 version. Please use the year 2018 version (the City of Tucson adopted the 2018 iCodes).
3. You listed Soils, Concrete Testing, Concrete Construction, Masonry & Structural Steel as required special inspections under CATEGORY within the form. However, no field reports were submitted. Per International Building Code section 1704, Inspection Field Reports are to be filed/submitted with the Building Official. Please submit all field reports enumerated on the list.
4. Please resubmit.
10/23/2024 PDSD Application Completeness Express REVIEW COMPLETED