Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0823-02097
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/06/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
09/13/2023 | Site Engineering | REQUIRES RESUBMIT | 1. The permit cannot be approved until its associated development package, TD-DEV-0723-00325, has been approved. Lianne Evans lianne.evans@tucsonaz.gov |
||
09/21/2023 | Site Zoning | REQUIRES RESUBMIT | FROM: Paul Camarena PDSD Zoning Review Section PROJECT: TC-COM-0823-02097 870 E TUCSON MARKETPLACE BL Zoning PAD-15 TRANSMITTAL DATE:September 21, 2023 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1.COMMENT: Zoning has reviewed the building plan for compliance with TD-DEV-0723-00325, Zoning cannot approve the building plans until the DP is approved. 2.COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP. If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov |
||
09/28/2023 | Water - PDSD | REQUIRES RESUBMIT | 1. The water service to the proposed hospital does not appear to comply with the requirements of Section 609.2, IPC 2018 with regard to having, “…two water service pipes installed in such a manner so as to minimize the potential for an interruption of the supply of water in the event of a water main or water service pipe failure.” Contact Tim Rowe (tim.rowe@tucsonaz.gov, 520-242-3005), Tucson Water New Development, for assistance in selecting appropriate connection points to the water mains. 2. Provide the total water demand that will be served by either of the proposed water meters. Reference: Section 107.2.1, IBC 2018. |
||
10/06/2023 | External Reviewers - Willdan | REVIEW COMPLETED | |||
09/29/2023 | Fire New Construction | REVIEW COMPLETED | |||
08/30/2023 | PDSD Application Completeness | REVIEW COMPLETED |