Permit Number: TC-COM-0823-02094
Parcel: 125101380

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0823-02094
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/22/2025 Commercial Mechanical Standard APPROVED Mechanical (M) Reviewer
Keith Miller; kmiller@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 12/20/2025
The mechanical review is approved. Subject to the field inspector’s approval.
12/22/2025 Commercial Plumbing Standard APPROVED Plumbing (P) Reviewer
Keith Miller; kmiller@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 12/20/2025
The plumbing review is approved. Subject to the field inspector’s approval.
12/31/2025 Outdoor Lighting Standard APPROVED Approved with notes added to Sheet E-201.
12/19/2025 Site Engineering Standard APPROVED
01/08/2026 Water - PDSD Standard APPROVED
01/09/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/22/2025 Commercial Building Standard REQUIRES RESUBMIT Structural (S) Reviewer
Keith Miller; kmiller@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 12/20/2025
The structural review is approved. Subject to the field inspector’s approval.

Building (B) Reviewer
Keith Miller; kmiller@safebuilt.com
Discipline Status:Denied
Date Completed: 12/20/2025
1.Sheets G-000, G-003 / Floor Plan / Incorrectly calculated occupant load.The concentrated occupant area (standing)
at 1 occupant per 5sf is to be calculated using the floor space up to the ordering counter. The break room with tables
and chairs is to be calculated at 1 occupant per 15sf. Correct and coordinate the occupant load calculations, plumbing
fixture count, and egress calculations on sheet G-003 with the load specified on sheet G-000. (2018 IBC section 1004)
2.Sheet A-604 / Architectural interior elevations / The revised interior elevations were not provided in the revised set.
Provide the full set of sheets affected by the revisions. (2018 IBC section 107)
12/22/2025 Commercial Electrical Standard REQUIRES RESUBMIT Electrical (E) Reviewer
Keith Miller; kmiller@safebuilt.com
Discipline Status:Denied
Date Completed: 12/20/2025
1.Sheet E-201A / Dining Power Plan / Inconsistent layout.The electrical panels and room do not match the design
shown on other sheets. Correct and coordinate all drawings. (2018 IBC section 107)
2.Sheet E-204 / Roof Power Plans / Missing roof receptacles.Show the locations of the rooftop maintenance
receptacles as referenced in Keynote #6 and Panel D circuit #24. (2017 NEC section 210.63)
3.Sheet E-302 / Single Line Riser Diagram / Missing the date of revision #5. Includethe date of revision #5 in the title
block. (2018 IBC section 107)
01/09/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-0823-02094 – TD-DEV-0123-00102
3605 E. Broadway Blvd. Tucson, AZ 85716
Chic-Fil-A Remodel (1st Review)

TRANSMITTAL DATE: 1/9/2026

This site is located in the C-2 zone (UDC 4.7.21). Food Service is a permitted use subject to Use Specific Standards 4.9.4.M.1 and 4.9.13.P.

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: While the plans appear to match TD-DEV-0123-00102, Site Zoning cannot approve this permit until the associated Development Package has been approved by all review agencies.
2. Comment: Additional comments may be forthcoming on the next review based on the plans submitted and responses to zoning review comments.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
01/08/2026 Fire New Construction Standard REVIEW COMPLETED
12/18/2025 PDSD Application Completeness Express REVIEW COMPLETED